Geniox user manual

Table Of Contents
28
| Instructions for unloading on the site as well as installation and connection
H.3.1 Description
The position of components is shown and described in Annex 2.
Connections to terminals are shown in the wiring diagram.
When control of constant pressure in the ducts (also called demand controlled capacity) is required, the pressure trans-
mitters must measure in the duct system at places where all pressure changes can be registered accurately for reliable
pressure control. This placement is left to the customer’s free choice.
It is important to achieve a constant pressure also for the most faraway diffusers.
H.3.2 Wiring diagrams
The wiring diagrams are printed in separate manuals delivered with the units.
The wiring diagrams are not unique for the order specific units, but it is standard wiring diagrams with data about all
configurations of the units. Hereby the wiring diagrams will inform about components that are not ordered and deliv-
ered. See the order confirmation and Annex 2 with exact information about the accessory components that are ordered
and delivered.
The wiring diagram includes:
General description
Circuit diagrams
Cabinet layout
Terminal matrix
Cable plan
H.3.2.1 Labels on or with the cabinet
Label with data about the cabinet including data about fuses see chapter C.2.2
Flowchart see the example inchapter C.2.3 unique flowchart for the order specific unit is shown in annex 2 with
the unique production number of the unit
Label with an example of the terminal plan for external components is shown in chapter C.2.5 the unique terminal
plan for external components for the order specific unit is shown in annex 2 with the unique production number of
the unit.
In chapter C.2.5 is for the Access control board shown a drawing of the control board with the terminals and this is just
an example, and not unique for the order specific unit.
H.3.3 Installation of mains power supply
An AC/DC residual current device must be installed in the power supply. The power supply for the units is 3*400 V + N
+ PE - 50 Hz. Protection of the units in accordance with the local statutory requirements for the additional protection of
systems with frequency converters and EC fans. The operator is responsible for the installation of the necessary protec-
tion equipment (supply disconnecting device is not delivered by Systemair).
output | 11