| Instructions for unloading on the site as well as installation and connection
Bracket inside a section. A similar bracket is installed in
the next section. This is the bracket in the Geniox sizes 10
and 18
Press the sections hard together so that the rubber pro-
files are so flat that the iron frames of the two sections
are joined. Strap with tensioner is suitable for pressing
the sections hard together.. Note! Do not place the strap
on the vertical profiles. To avoid any load and stress on
the vertical profiles the strap must be carefully placed
on the bottom profiles of the unit.
The sections must then be locked permanently together
with 8 mm bolts. Nut with threat is installed from the fac-
tory in one of the brackets
Note! Do not pull the sections together by tensioning
the 8 mm bolts. Use the strap for this purpose.
Brackets inside a section. Similar brackets are installed in
the next section. These are the brackets in the Geniox
sizes 20 to 31
Press the sections hard together so that the rubber pro-
files are so flat that the iron frames of the two sections
are joined. Strap with tensioner is suitable for pressing
the sections hard together.. Note! Do not place the strap
on the vertical profiles. To avoid any load and stress on
the profiles the strap must be carefully placed on the
bottom profiles of the unit.
The sections must then be locked permanently together
with 8 mm bolts. Nut with threat is installed from the fac-
tory in one of the brackets
Note! Do not pull the sections together by tensioning
the 8 mm bolts. Use a strap for this pupose.
H.2.9 Fitting the ductwork
Flexible duct connections between AHU and ductwork must always be installed. Be sure that flexible duct connections
are almost fully stretched. (Flexible connections are ordered as accessories and they are placed inside the unit). Avoid
blockage and turbulence at the fan outlet.