Geniox user manual

Table Of Contents
Instructions for unloading on the site as well as installation and connection |
23
Assembly has been completed successfully
The grey guiding and connection blocks might be installed
inside the units on the vertical profiles. Press the sections
hard together so that the rubber profiles are so flat that
the iron frames of the two sections are joined. Strap with
tensioner is suitable for pressing the sections hard to-
gether.. Note! Do not place the strap on the vertical pro-
files. To avoid any load and stress on the profiles the
strap must be carefully placed on the bottom profiles of
the unit.
The sections must then be locked permanently together
with 8 mm bolts and nuts through the grey guiding and
connection blocks. Systemair have provided you the 8
mm bolts with round heads and nuts required to carry this
task out. An Allen key size 6 will be required.
Note! Do not move the sections together by tensioning
the 8 mm bolts and nuts. Tighten the straps for this
purpose.
If none of the above mentioned grey guiding and connec-
tion blocks are installed this alternative method must be
used. Demount the doors and lock the two sections per-
manently together with self-drilling screws. Self–drilling
screws are delivered with the unit. It might be necessary
to use clamps to hold the sections fully together prior to
tightening the screws.