| Instructions for unloading on the site as well as installation and connection
The sections are then to be positioned directly opposite
each other. If the sections are built with legs, the adjust-
able feet can be used to get the sections in line and at the
same height.
Press the sections hard together so that the rubber pro-
files are so flat that the iron frames of the two sections
are joined. Strap with tensioner is suitable for pressing
the sections hard together.. Note! Do not place the strap
on the vertical profiles. The strap must be carefully
placed on the bottom profiles of the unit.
The sections must then be locked permanently together
with 8 mm bolts and nuts through the grey guiding and
connection blocks. Systemair have provided you the 8
mm bolts with round heads and nuts required to carry this
task out. An Allen key size 6 will be required.
output | 11