Instructions for unloading on the site as well as installation and connection |
21
Note! Place the strap on the bottom profiles of the unit to avoid any load and stress on the vertical profiles when
sections are pulled together along the base frame or on the floor. The sections must be pulled fully and tight togeth-
er with the strap placed on the bottom profiles.
Sections are mounted to base frames with self-drilling screws. In the base frame you will find a sufficient number of 5
mm holes that are prepared for the self drilling screws. In this picture you are standing and you are watching the as-
sembled base frame on the floor or roof.
Use self-drilling screws 4,8 X 18 mm to be screwed upward through the holes into the bottom profile of the air
handling unit Note! A screw must be placed in every hole to achieve the necessary strength. In this picture you are ly-
ing on the floor or roof looking upward under the base frame. The screws will not be visible, when you are standing be-
side the unit looking at the unit
H.2.8 Joining the AHU sections
The sections must be placed on the base frame and if the unit is delivered with 150 mm legs, the sections must be posi-
tioned directly in line with each other.
Ensure that the internal factory-fitted rubber sealing is undamaged