| Unintended use and misuse inappropriate applications for the machine
Intended applications for the units are:
Offices
Teaching rooms
Hotels
Shops
Homes and similar comfort zones
The majority of rooms at clinics and hospital where extended requirements according to Eurovent level 1, 2 and 3
are not requested
G Unintended use and misuse inappropriate applications for the machine
Units for outdoor installation must be specified and ordered for outdoor installation. The units must not be used in envi-
ronments that exceed corrosion class C4 according to EN ISO 12944-2, and for transport of solid particles.
Examples of not intended use:
Kitchen extraction
swimming pools
off-shore
Ex-areas
drying of washed clothes.
Do not use the unit with partly finished duct systems.
Do not use the unit for ventilation of the building site until the unit is properly provided with guards.
G.1 Air handling unit in operation
The pressure difference between interior and exterior of the unit must not exceed 2000 Pa for the Geniox 10 and up to
Geniox 31 (including Geniox 31).
Before start-up of the unit all ducts, safety guards and all protective devices must be mounted to prevent any access to
rotating fan impellers. All inspection doors must be closed and locked when the unit is in operation.
Do not use the unit without filters.
H Instructions for unloading on the site as well as installation and connection
H.1 Unloading on the site
The air handling unit AHU - is delivered as one section or in several sections, which are to be assembled on site. The
AHU is delivered on transport pallets, legs, base frame with brackets for lifting or base frames with holes for forks on
forklifts. Loading and unloading as well as transport on the site is possible by fork-lift truck or by crane using suitable
lifting straps.
H.1.1 Handling methods
Possible ( ) and not possible ( ) handling methods are described in the table below.
Type
Handling methods
Forklift Lifting by
straps
Brackets at
base frame
for lifting
Hoist holes
in base
frames
Holes in
base frames
for forks
(option)
Corners in
sections for
lifting
Hoisting
pipe
Sections on
pallets
Sections on
base frames
Unit on
base frame