Geniox user manual

Table Of Contents
13-2
| Connection of fan motor and set-up manual for frequency converter
3-03: Maximum Reference: Max. Hz from order papers
3-16 + 3-17: Reference 2- and 3 Source: [0] No function
3-41 + 342: Ramp 1 up and down: 20 Sec.
4-19: Max. Output Frequency: 90Hz
4-14: Motor Speed High Limit: 90Hz
4-18: Current limit: 100 %
5-12: Terminal 27 Digital input: [0] No operation
5-40.0: Function Relay: [3] Drive ready/remote
5-40.1: Function Relay: [3] Drive ready/remote
6-25: Terminal 54 High Reference: Max. Hz from order papers
14-03: Over modulation: [1] Active
14-20: Reset Mode: [2] Automatic reset x 2
0-50: LCP Copy: [1] All to LCP (Copy of Systemair factory settings to panel)
Connections:
0-10V: terminal 54-55
Start: terminal 12-18
Thermistor: terminal 50-53
Drive ready: terminal 1-2
13.3 AC-fan operation without thermistor for Danfoss FC101
Systemair factory set-up is based on Danfoss initialization.
14-22: Operation mode: [2] Initialisation (Danfoss Initialisation)
Turn power off and on.
Systemair factory set-up:
0-01: Language selection:
1-03: Torque characteristic: [3] Auto-Energy optim.
1-20: Motor power: According to motor plate
1-24: Motor Current: According to motor plate
1-25: Motor Nominal Speed: According to motor plate
1-29: Automatic motor adaption (AMA): [1] Compl.motor adaption to (Turn power off and on.)
1-42: Motor Cable Length: Order specific
1-50: Motor Magnetisation at zero speed.: 0 %
1-52: Min. Speed Normal Magnetisation: 10 Hz
1-73: Flying start: [0] Deaktivated
5-40.0: Function Relay: [3] Drive ready/remote
14-03: Over modulation: [1] Active
14-20: Reset Mode: [2] Automatic reset x 2
0-50: LCP Copy: [1] All to LCP (Copy of Systemair factory settings to panel)
Connections:
output | 11