Geniox user manual

Table Of Contents
10-29
| Speed control for rotor and assembly of divided rotor
10.5.2.10 Mount seals
Middle seal Z-plates depending on intended air flow attach either to the horizontal or the vertical middle spar with the
supplied cutting screws.
The middle seals should lie at close as possible, but not drag. To check the proper setting, the rotor should be turned
several times carefully by hand.
Fasten bearing box seals with cutting screws.
The circumferential seals are held by spring clamps and further secured by an additional spring steel sheet. The rubber
seal is pushed gently up against the rotor with a screwdriver. The circumferential seal is pushed back slightly by the
rotating rotor, thereby bringing it into optimal operational position.
10.5.2.11 Duct connections
When mounting the ducts to the rotor system casing, make sure that no forces act on the casing that could change the
casing position. In critical situations, we recommend installing elastic studs between rotor casing and air duct.
output | 11