Speed control for rotor and assembly of divided rotor |
10-28
10.5.2.8 Mount rotation sensor
Attach the holder for the rotation sensor into the rotor system encasing so that after the mounting of the rotation
sensor, a gap of 5–8 mm can be made between magnet and rotation sensor.
The magnet of the pulser i.e. the rotation sensor has to be screwed onto the circumference panel of the heat
exchanger. Make sure that only the circumference panel of the rotor and not the accumulator is drilled into.
In most cases, the circumference panel of the rotor is made of aluminium. The magnet can be screwed directly to the
circumference panel.
If the circumference panel is made of magnetic metal, then an insulating buffer needs to be attached between the
magnet and the circumference panel.
10.5.2.9 Mount mounting corner
Insert the mounting corner again and fasten to the casing frame with the appropriate screws