Geniox user manual

Table Of Contents
Speed control for rotor and assembly of divided rotor |
10-10
Register
Address
Type
Description
Extended SW version
FrontendVersion
0x320 0X333 R
Frontend software version C string.
BackendVersion
0x334 0X347 R
Backend software version C string.
10.2.5 Modbus control Normal operation
Write the speed reference in SpeedSet between 0 and 1000 (0–100%). Note that the conversion from Speed Set to
rpm speed is non-linear. The reference in rpm can be read using register SpeedSetScaled. The minimum and maximum
speed can be read in registers MinSpeed and MaxSpeed.
Start the motor by setting Operation to 1. Stop it by setting it to 0. You can change the speed while the motor is
running.
If communication with the device is stopped, a warning will appear after 10 seconds but the motor will keep running.
Faults and warnings can be reset by setting operation to 8.
10.3 Assemble divided rotor and the Systemair casing
Half of the rotary heat exchanger is pre-assembled from Sytemair with centre of the rotor as well as bearings in the
centre installed in the lower half of the unit section.
Size
A B C
Geniox 22 2282 1764 500
Geniox 24 2482 1864 500
Geniox 27 2782 1964 500
Geniox 29 2982 2064 500
Geniox 31 3182 2164 500
Geniox35 3482 2718 1082
Geniox38 3482 3018 1082
Geniox41 4082 3018 1082
Geniox44 4082 3018 1082
Remove the Systemair ceiling panel from the lower half of the Systemair unit section for free access to mount the
upper half of rotor casing. With the upper half of the rotor casing properly mounted, the next step is to mount the radial
walls to the flanges on the center. The radial walls are placed between the rotor segments.
output | 11