Geniox user manual

Table Of Contents
10-3
| Speed control for rotor and assembly of divided rotor
10.1.3 Information about connection of cables to terminals on the control board in RHC 200
delivered before 2021
Connection of cables to the terminals on the board
Terminal
Connection
1
Earth supply
2
Earth supply
3
Fase supply
4
Neutral supply
5
Rotor turns upwards seen from inspection side
Terminal 5 = wire 1
Terminal 6 = wire 2
Terminal 7 = wire 3
Rotor turns downwards seen from inspection
side
Terminal 5 = wire 2
Terminal 6 = wire 1
Terminal 7 = wire 3
6
7
8
Earth for rotor motor
Test
Set DIP switch 4 in position ON and press the button for test. The signal is controlled by the
potentiometer at constant speed and not by any signal from the control system.
Adjust Is activated by setting DIP switch 4 at OFF and DIP switch 5 at ON. Hereby the maximum
revolutions can be adjusted between 50 and 100 % by the potentiometer. Usually, the factory
setting is OK, but with this potentiometer the maximum revolutions can be reduced or increased.
9
Alarm signal COM (common)
10
Alarm signal Relay is normally closed (this is used by the control system from Systemair)
11
Alarm signal Relay is normally open (this is not used by the control system from Systemair)
12
Control system input is 0 —10 volt DC
13
Control system input ground
14
Rotor guard (black cable from rotor guard from Systemair)
15
Rotor guard (blue cable from rotor guard from Systemair)
16
Rotor guard (brown cable from rotor guard from Systemair)
17
For BUS signal RS485 A (green wire from Systemair control system)
18
For BUS signal RS485 B (yellow wire from Systemair control system)
19
For BUS signal ground (white wire from Systemair control system)
output | 11