Installation of steel roof in the sizes 10 44 |
9-8
9.9 Mount roof plates some of them are overlapping by 2 ribs
The width of each plate is always 1025 mm and some of the plates have to overlap by 2 ribs to achieve the optimal
total length of the whole roof see the illustration above.
9.10 Mount overhang profile G5 on the other end of the unit
When the last trapezoidal plate (in this example F5) has been placed on the unit, the second roof overhang profile G5
must be pushed under the trapezoidal roof plate and mounted with the self-drilling, painted screw with sealing washer.
Mounting must be similar to the mounting of roof overhang profile under the trapezoidal roof plate at the other end of
the unit.
9.11 Mount side profiles and corners along the edges of the roof to protect persons
Profiles N and O with the rectangular holes are for the long and lower side of the roof because rain can escape through
the holes. Mount the profiles type N first and the profile O last because the profile O goes over the profile N. Mounted
in this order, the profile O can match the end of the roof and the surplus length of the profile O will just cover part of
the previous profile N. Mount the profiles L and M along the long and higher front side of the roof. Mount the 4
protection corners.