Geniox QuickGuide uk 08 2017

Directives. Geniox fulfils the
following directives:
• Machinery Directive 2006/42/EC
• Ecodesign Directive 1253/2014
• EMC Directive 2014/30/EU
• Low Voltage Directive 2014/35/EU
Pressure Equipment Directive
2014/68/EU.
Classifications
The performance of the air handling unit casing corresponds
with the following classifications according to the European
standard EN 1886, 2nd edition 2008.
Operating pressure
Difference between surrounding and pressure inside the air
handling unit:
0 - 2000 Pa (Geniox 10-31)
0 - 1500 Pa (Geniox 36-44).
Operating temperatures
General temperatures for the air in the air handling unit:
Standard design: -40/+40 ˚C
Special design: -40/+60 ˚C.
Filter by-pass leakage
Negative pressure:
- 400 Pa: Class G1-F9
Positive pressure:
+ 400 Pa: Class G1-F9.
Roof unit. Geniox are available as roof
units, designed for outdoor installation. In
this version the unit is assembled on a
base frame. The roof unit can be deliv-
ered with two different types of roofing:
Steel profile roof, aluzinc protected cor-
rugated steel sheets, and profiles for fas-
tening and finishing the roofing.
PVC roof, very easy to handle and has a
good weather protection.
Eurovent certification
Geniox is constructed in accordance
with European standards and is
certified by Eurovent.
Geniox Quick guide | 7