Ecodesign QuickGuide uk

Pressure gauge
(Exclusively for 2018).
If the air handling unit has filters
installed, they must be equipped
with a visual alarm signal or an alarm
in the control system, if the pressure
drop across the filter exceeds the
maximum allowed pressure drop.
SFPint in W (m
3
/s)
The SFP Internal calculation is based
on the pressure drop in the following
components:
• Filter pressure drop
Pressure drop across the heat
recovery system
• Pressure drop across the fans.
For calculation of the SFP Internal, the
air handling unit is compared to a
standard configuration, which is an F7
filter in the supply air and an M5 filter
in the extract air.
By missing or lower filter classes, a
penalty is added to the filters pres-
sure drop. Thus, the actual value is
increased as well as the limit value is
lowered.
Example: If the air handling unit has
an M6 filter in the supply air and an
M5 filter in the extract air, the air
8
handling unit receives a calculative
penalty, which causes that the pres-
sure drop for the supply air filter is
calculated with 200 Pa.
Thus, the SFP Internal value is incre-
ased, and the limit value is lowered
with 200 points. Therefore, it will be
difficult to comply with the limit value.
This also applies to the extract air
filter. The ‘penalty is 160 Pa, if the
filter is missing or the filter class
is lower than M5.
If more efficient filters than F7 and
M5 are selected, the calculation of
SFP Internal is still based on the pres-
sure drop for respectively F7 and M5.
In this way, more efficient filters can
be selected without affecting the SFP
internal.
Approved’, ‘Failed’ or ‘Warning’
If all requirements are fulfilled, the
function is marked as ‘Approved’.
If one or more requirements are not
fulfilled, the function is marked with
a ‘Warning’ or ‘Failed’
‘Warning’ is displayed, if you need
to pay special attention to
something. Usually, to point out that
the fans must be equipped with
variable speed drive (frequency
converter).
‘Failed’ usually means that the effi-
ciency in the chosen configuration is
not ok. The air handling unit then
needs to be further optimised.
Total check
Approved’All Ecodesign require-
ments are fulfilled.
‘Failed’ – One or more requirements
are not fulfilled. The air handling unit
is illegal to install and operate accor-
ding to Ecodesign.
Technical specification
Additional technical specification that
must be documented from the
manufacturer according to Ecodesign
Directive 1253/2014.
30-03-2017 Air handling unit design | SystemairCAD 2.0 Version C2017-04.00.00-beta07 | Geniox Comfort 12DR
| Project:
| 2/2
Ecodesign
2016 Value Limit 2018 Value Limit
Unit type (Non Residential - Bidirectional) Approved Approved
Fan with multispeed or Var.Speed Drive Approved Approved
Heat recovery Approved Approved
Thermal efficiency of Heat Recov. System Approved 80.8 67.0 Approved 80.8 73.0
Pressure gauge (exclusively for 2018) Approved Approved
SFPint in W/(m³/s) Approved 904 1414 Approved 904 1134
Total check Approved Approved
Supply Extract
Manufacturer Systemair
Model Geniox Comfort 12DR
Typology NRVU;BVU
Drive Type VSD VSD Installed
Type of Heat Recovery System (HRS) Rotary heat exchanger
Thermal efficiency of HRS (dry condition) 80.8 %
Non Residential unit - flow rate 1.33 1.33 m³/s
Effective electric power input incl. clean filters and variable drive 1.36 1.30 kW
SFPint in W/(m³/s) 2016 904 469 436 W/(m³/s)
SFPint in W/(m³/s) 2018 904 469 436 W/(m³/s)
Face velocity 2.03 2.03 m/s
Nominal external pressure 300.00 300.00 Pa
Internal pressure drop of ventilation components 268.84 245.93 Pa
Overall static pressure drop with clean filter 585.26 549.21 Pa
Overall static efficiency of fans with clean filter 57.30 56.45 %
Maximum external leakage rate Leakage class L2 according to EN 1886. Leakage rate is less than 1%.
Maximum internal leakage rate Leakage rate is less than 3%.
Energy class for filters B D
Visual filter warning description Control display
Internet address with information about disassembly techdoc.systemair.dk
Sound power level
Total
Supply air
82 dB(A)
Outdoor air
67 dB(A)
Exhaust air
84 dB(A)
Extract air
67 dB(A)
Sound break out
79 dB(A)
Ecodesign is calculated for a reference configuration with F7 filter in supply and M5 filter in extract.
Printout from SystemairCAD with extra mandatory technical documentation in accordance with Ecodesign.
5
6
7
8
4
|
Ecodesign in SystemairCAD