Commissioning Record
Table Of Contents
Function settings
|
5
Function
Default setting Set value
Freeze protection
Type of freeze protection
□ None
□ Temp. sensor
□ Guard
□ Temp. sensor + guard
None
Temp. sensor
Guard
Temp. sensor + guard
Alarm limit when unit is running
7 °C
°C
P-band when unit is running
5 °C
°C
Set point when unit is stopped
25 °C
°C
HW pump control
Pump running mode
⊠ Auto
□ Always running
Auto
Always running
Type of feedback
⊠ None
□ Alarm
□ Run indication
None
Alarm
Run indication
Pump stop delay
5 min
min
Pump running when outdoor temp. is
below:
10 °C
°C
Hysteresis to allow pump stop
1 °C
°C
C.3 General
Function
Default setting
Set value
General
Extended operation stop delay 0 min
Warm start when outdoor temp. is
below:
8°C
CO
2
control
□ No
□ Fan start/stop
□ Mixing damper function
□ Fan start/stop + mixing damper
No
Fan start/stop
Mixing damper function
Fan start/stop + mixing damper
Supply air fan set point when CO
2
control
□ Low
□ Normal
⊠ High
Low
Normal
High
Extract air fan set point when CO
2
control
□ Low
□ Normal
⊠ High
Low
Normal
High
Start limit fan start/stop
1000 ppm
ppm
Setpoint mixing damper
800 ppm
ppm
90925501 |