Commissioning Record

Alarm configuration |
49
Alarm settings Def. settings
Set value
Alarm number 214
Alarm name Deviation alarm supply temp zone 2
Action: No action
Level:
B
Delay:
30 m
Limit: 10°C
Alarm number 215
Alarm name Deviation alarm supply temp zone 3
Action: No action
Level:
B
Delay:
30 m
Limit: 10°C
Alarm number 216
Alarm name Freeze protection alarm zone 1
Action:
Fast stop
Level:
A
Delay:
1 s
Alarm number 217
Alarm name Freeze protection alarm zone 2
Action:
Fast stop
Level:
A
Delay:
1 s
Alarm number 218
Alarm name Freeze protection alarm zone 3
Action:
Fast stop
Level:
A
Delay:
1 s
Alarm number 219
Alarm name Electric heater is overheated zone 1
Action:
Normal stop
Level:
A
Delay:
1 s