Commissioning Record

26
| Alarm configuration
Alarm settings Def. settings
Set value
Alarm number 83
Alarm name Deviation alarm extract air fan
Action: No action
Level:
-
Delay:
30 m
Limit: 50 Pa
Alarm number 84
Alarm name Deviation alarm humidity control
Action: No action
Level:
-
Delay:
30 m
Limit: 10%
Alarm number 85
Alarm name Deviation alarm extra controller
Action:
Fast stop
Level:
-
Delay:
0 s
Limit: 10°C
Alarm number 86
Alarm name High supply air temperature
Action:
Normal stop
Level:
A
Delay:
300 s
Limit: 35°C
Alarm number 87
Alarm name Low supply air temperature
Action:
Normal stop
Level:
A
Delay:
300 s
Limit: 10°C
90925501 |