Commissioning Record

Alarm configuration |
21
Alarm settings Def. settings
Set value
Alarm number 54
Alarm name Filter alarm extract air
Action: No action
Level:
B
Delay:
300 s
Limit:
Alarm number 55
Alarm name Alarm low air flow
Action:
Normal stop
Level:
A
Delay:
30 s
Alarm number 56
Alarm name Freeze protection guard
Action:
Fast stop
Level:
A
Delay:
1 s
Alarm number 57
Alarm name Defrosting guard exchanger
Action: No action
Level:
C
Delay:
0 s
Alarm number 58
Alarm name Fire alarm
Action:
Fast stop
Level:
A
Delay:
1 s
Alarm number 59
Alarm name Smoke alarm
Action:
Fast stop
Level:
A
Delay:
1 s
90925501 |