GENIOX SOFTCOOLERV1

4
| Technical Data
Mats Sándor
Technical Director
3 Technical Data
3.1 Unit size and Compressor(s)
One frequency-controlled compressor is supplied in all unit sizes.
Unit size
Power
range
Cooling
capacity
kW
400V 230V
Compressor Power
frequency
converter
Main
swich
Compres-
sor
Power
frequency
converter
Main
swich
12 2 21 VZH044CG
10 kW
25 A VZH044CJ
10 kW
63 A
14
1 21 VZH044CG
10 kW
25 A VZH044CJ
10 kW
63 A
2 28,7 VZH052CG
11 kW
63 A VZH052CJ
11 kW
80 A
16
1 28,7 VZH052CG
11 kW
63 A VZH052CJ
11 kW
80 A
2 37,5 VZH065CG
15 kW
63 A VZH065CJ
15 kW
80 A
18
1 37,5 VZH065CG
15 kW
63 A VZH065CJ
15 kW
80 A
2 48,5 VZH088AG
15 kW
63 A VZH088BJ
15 kW
125 A
20
1 48,5 VZH088AG
15 kW
63 A VZH088BJ
15 kW
125 A
2 60,7 VZH117AG
18,5 kW
63 A VZH117BJ
18,5 kW
125 A
22
1 60,7 VZH117AG
18,5 kW
63 A VZH117BJ
18,5 kW
125 A
2 73,9 VZH170AG
22 kW
80 A VZH170BJ
22 kW
170 A
24 2 88,2 VZH170AG
22 kW
80 A VZH170BJ
22 kW
170 A
3.2 Refrigerant
The refrigerant used for Geniox Softcooler is R410A. This is initially filled at the factory, and the relevant quantity is indi-
cated on the cooling section. A long-term test is carried out with a vacuum to ensure that the cooling circuits are com-
pletely free of leaks before refilling with R410A.
4 Delivery, Transport, Storage
4.1 Transport and storage
Caution
As for all equipment with electrical components, it is important that the cooling section is not stored
outdoors. Water and condensation may, in the worst case, lead to full short circuit and breakdown when
the power is connected. If the unit must be stored outdoors, ensure that it is protected against rain and
allow air to circulate to prevent condensation.
The Geniox Softcooler should be stored and transported in such a way that it is protected against physical damage that
can harm panels etc. It should be covered so dust, rain and snow cannot enter and damage the unit and its
components.
Important
Use the packaging exclusively as transport protection and not as a lifting aid.
When lifting with forklift trucks or pallet jacks, ensure that the forks go under the entire length of the box,
otherwise the underside of the box may be damaged. When using a crane, straps must be secured to
legs or any pallets; it is important that the straps do not slip during lifting.
Be particularly aware that the cooling section may have a high centre of gravity if the compressor is
positioned at the top of the cooling section.
212930 | A001