Table Of Contents
Commissioning
|
7
2. Press the sections hard together so that the rubber profiles are so flat that
the iron frames of the two sections are joined. Strap with tensioner is suit-
able for pressing the sections hard together.. Note! Do not place the strap
on the vertical profiles. The strap must be carefully placed on the bottom
profiles of the unit.
The sections must then be locked permanently together with 8 mm bolts
and nuts through the grey guiding and connection blocks. Systemair have
provided you the 8 mm bolts with round heads and nuts required to carry
this task out. An Allen key — size 6 — will be required.
3. Fit the supplied handles.
4. Adjust doors if necessary.
5. Fit the supplied water trap.
The height of the water trap is already adjusted to match the height of sup-
plied feet or base frame.
6.1 Electrical Connection
Warning
• Make sure that the mains supply to the unit is disconnected before performing any maintenance or
electrical work!
• All electrical connections and maintenance work must be carried out by an authorized installer and in
accordance with local rules and regulations.
Important
• Make sure that the voltage in the building is checked against the marking on the unit.
Geniox Softcooler is delivered completely wired, which means that the electrician is only required for connection to the
mains. Geniox Softcooler is delivered in all sizes, with an external safety switch, which cuts all phases and power supply
when switched off. This is the connection point for the electrician. The safety switch is not fixed in place on delivery
due to transport. The safety switch must be fitted on the front of the unit. Wires from the cooling section are routed to
the safety switch.
6.1.1 Rotational direction of compressor(s)
On Geniox Softcooler with one compressor, the rotational direction of the compressor is taken care of using a frequency
converter and rotational direction is independent of the phases of the main switch.
Note:
Unit, Geniox Softcooler and any electrical batteries are made for separate power supply, which is basically
sensible considering that these are high currents and require cables with a large cross-section. However, if
desirable, it is possible to pull one main cable out and divide conduits at the unit. Dimensioning of the
conduit can also be drawn according to either the unit + electrical battery or unit + Geniox Softcooler, or
according to which has the greatest power. This is possible as there is never simultaneous acceleration for
the electrical battery and cooling.
7 Commissioning
7.1 Before start-up
• Correct voltage connected.
• Safety switches and fuses on.
• Visual check of the unit, no loose objects, everything electric connected.
• Drain trap fitted.
7.2 Control of Geniox Softcooler
The Geniox Softcooler cooling section is controlled as needed from the main controller.