Geniox GO User manualv7.2
Table Of Contents
- A Manufacturer
- B Name of machines
- C Declaration of Conformity
- D General descriptions, dangers and warnings
- E The control panel for the control system.
- F Drawings, diagrams, guides and instructions for the use, maintenance and repair
- G Employees in charge of operation/control/maintenance
- H Unintended use and misuse – inappropriate applications for the machine
- I Instructions for unloading and handling on site
- J Installation
- J.1 Installation - mechanical
- J.1.1 Free area in front of and above the unit
- J.1.2 Supporting surface
- J.1.3 Adjustable feet under legs or base frame and transport of sections
- J.1.4 Base frame assembly
- J.1.5 Base frames for outdoor units
- J.1.6 Outdoor units — support under the base frame of the unit
- J.1.7 Installation on the site of unit sections at the base frame when sections are delivered on pallets
- J.1.8 Joining the unit sections
- J.1.9 Fitting the ductwork
- J.1.10 Risk of stack effect by vertical ducts and wind pressure on louvers
- J.1.11 Door alignment
- J.1.12 Lock the doors by using the key
- J.2 Installation - electrical
- J.3 Installation – Pipes for water – hot and chilled, valves and drains
- J.1 Installation - mechanical
- K Installation and assembly instructions for reduction of noise and vibration emissions
- L Start-up, adjustments, use and commissioning
- M Information about the residual risks
- N Instructions on the protective measures during repair and maintenance
- O The essential characteristics of tools which may be fitted to the machinery
- P The conditions of stability during use, transportation, assembly, dismantling when out of service
- Q Instructions for machinery where these are regularly to be transported
- R The operating method to be followed in the event of breakdown. Safe restart.
- S Adjustment and maintenance operations
- T Instructions to enable adjustment and maintenance safely
- U Information on airborne noise emissions exceeding 70 dB(A)
- Annex 1 Technical data – unique data for every unit (in separate cover)
- Annex 2 Assembly of base frame – height 118 mm for unit sizes 10 – 18
- Annex 3 Assembly of base frame – height 118 mm for unit sizes 20 – 27
- Annex 4 Assembly of base frame – height 218 mm for unit sizes 10 – 18
- Annex 5 Assembly of base frame – height 218 mm for unit sizes 20 – 27
- Annex 6 Installation of steel roof in the sizes 10 – 31
- Annex 7 Speed control for rotor and assembly of divided rotor
- Annex 8 Reversible heat pump unit (in separate cover, if heat pump was delivered)
- Annex 9 Menu for internal controller in the heat pump unit (in separate cover, if heat pump was delivered)
- Annex 10 Connection of fan motor and set-up manual for frequency converter
- Annex 11 Commissioning protocol (in separate cover)
- Annex 12 Report with data from final functional test on the Systemair factory
- Annex 13 Short description of main components in the control system
- Annex 14 Wiring diagram (in separate cover)
- Annex 15 Operator’s guide (How to use the Systemair control panel) (in separate cover)
|
75
Register
Address
Type
Description
Extended SW version
FrontendVersion
0x320 — 0X333 R
Frontend software version C string.
BackendVersion
0x334 — 0X347 R
Backend software version C string.
7.1.1.2.5Modbus control — Normal operation
Write the speed reference in SpeedSet between 0 and 1000 (0–100%). Note that the conversion from Speed Set to
rpm speed is non-linear. The reference in rpm can be read using register SpeedSetScaled. The minimum and maximum
speed can be read in registers MinSpeed and MaxSpeed.
Start the motor by setting Operation to 1. Stop it by setting it to 0. You can change the speed while the motor is
running.
If communication with the device is stopped, a warning will appear after 10 seconds but the motor will keep running.
Faults and warnings can be reset by setting operation to 8.
7.2 Speed control RHC 200 delivered before March 2021
The cabinet with the speed control system for the rotor is installed behind the inspection door in the rotor section.
The cabinet contains the speed controller with all components, terminal blocks, LED displaying the operation mode, the
dual position DIP switch with 8 sliding levers for programming the rotor motor signal and a button for the activation of
the test mode.
7.2.1 Selection of correct signal via the 8 DIP switch levers
Position Function
Code
Up
Active = ON
1
Down
Deactivated = OFF
0
The factory sets the positions of the 8 DIP switch levers for the maximum of 10 revolutions per minute for standard
temperature exchangers and for hygroscopic exchangers. The position of each DIP switch lever is shown below.
Gen-
iox
GO
size
Diameter of
pulley
Diameter of
pulley
(Sorption)
DIP switch position
Motor
Motor (Sorption)
10 50 65 0000 90 TYD-S214–M 90TYD-
S214–M
11 50 85 120 TYD-S214–M
12 50 85
14 65 106
16 65 106
18 65 106 1000
20 71 118 0100 120 TYD-S214–M
22 80 140 120 TYD-S214–L
24 85 150
27 95 150
29 106 150
31 112 160
7.2.2 Indication of operation mode via red and green LED as well as test of motor
The LED is in the cover of the cabinet.
211728 | v7.2