Geniox GO User manualv7.2
Table Of Contents
- A Manufacturer
- B Name of machines
- C Declaration of Conformity
- D General descriptions, dangers and warnings
- E The control panel for the control system.
- F Drawings, diagrams, guides and instructions for the use, maintenance and repair
- G Employees in charge of operation/control/maintenance
- H Unintended use and misuse – inappropriate applications for the machine
- I Instructions for unloading and handling on site
- J Installation
- J.1 Installation - mechanical
- J.1.1 Free area in front of and above the unit
- J.1.2 Supporting surface
- J.1.3 Adjustable feet under legs or base frame and transport of sections
- J.1.4 Base frame assembly
- J.1.5 Base frames for outdoor units
- J.1.6 Outdoor units — support under the base frame of the unit
- J.1.7 Installation on the site of unit sections at the base frame when sections are delivered on pallets
- J.1.8 Joining the unit sections
- J.1.9 Fitting the ductwork
- J.1.10 Risk of stack effect by vertical ducts and wind pressure on louvers
- J.1.11 Door alignment
- J.1.12 Lock the doors by using the key
- J.2 Installation - electrical
- J.3 Installation – Pipes for water – hot and chilled, valves and drains
- J.1 Installation - mechanical
- K Installation and assembly instructions for reduction of noise and vibration emissions
- L Start-up, adjustments, use and commissioning
- M Information about the residual risks
- N Instructions on the protective measures during repair and maintenance
- O The essential characteristics of tools which may be fitted to the machinery
- P The conditions of stability during use, transportation, assembly, dismantling when out of service
- Q Instructions for machinery where these are regularly to be transported
- R The operating method to be followed in the event of breakdown. Safe restart.
- S Adjustment and maintenance operations
- T Instructions to enable adjustment and maintenance safely
- U Information on airborne noise emissions exceeding 70 dB(A)
- Annex 1 Technical data – unique data for every unit (in separate cover)
- Annex 2 Assembly of base frame – height 118 mm for unit sizes 10 – 18
- Annex 3 Assembly of base frame – height 118 mm for unit sizes 20 – 27
- Annex 4 Assembly of base frame – height 218 mm for unit sizes 10 – 18
- Annex 5 Assembly of base frame – height 218 mm for unit sizes 20 – 27
- Annex 6 Installation of steel roof in the sizes 10 – 31
- Annex 7 Speed control for rotor and assembly of divided rotor
- Annex 8 Reversible heat pump unit (in separate cover, if heat pump was delivered)
- Annex 9 Menu for internal controller in the heat pump unit (in separate cover, if heat pump was delivered)
- Annex 10 Connection of fan motor and set-up manual for frequency converter
- Annex 11 Commissioning protocol (in separate cover)
- Annex 12 Report with data from final functional test on the Systemair factory
- Annex 13 Short description of main components in the control system
- Annex 14 Wiring diagram (in separate cover)
- Annex 15 Operator’s guide (How to use the Systemair control panel) (in separate cover)
|
69
The cabinet contains the speed controller with all components, terminal blocks, LED displaying the operation mode, the
dual position DIP switches with 5 sliding levers for programming the rotor motor signal.
Through the different combinations of the 5 sliding levers of these dual position DIP switches, the correct signal is
available for the 3 different motors used for the 12 sizes of air handling units. The sliding levers are set and the function
is checked at the factory. The positions of the levers appear from the tables below.
7.1.1 Selection of correct signal via the 5 DIP switch levers in NOVA drive 370
Position Function
Code
Up — direction ON
Active = ON
1
Down — direction numbers
1, 2, 3, 4, 5
Deactivated = OFF
0
The factory sets the positions of the 3 DIP switch levers called 1, 2, 3 for the maximum about 14 revolutions per
minute for standard temperature exchangers. The position of each of the 3 DIP switches called 1, 2, 3 is shown
below.
Geniox GO
Diameter of pulley in
mm
Position for DIP switches called 1, 2,
3
Motor
10 70 000 90TYD-S214-M 2.8 Nm
11 70 000
12 77 000
14 70 100
16 77 100
18 95 100
20 106 010 120TYD-S214-M 5.5 Nm
22 118 010
24 118 010
27 118 110
29 106 001
31 112 001
DV 190 132 011 120TYD-S214-L 8 Nm
DV 240 150 011
The factory sets the positions of the 3 DIP switch levers called 1, 2, 3 for the maximum about 20 revolutions per
minute for sorption-hybrid exchangers as well as for sorption exchangers. The position of each of the 3 DIP switches
called 1, 2, 3 is shown below.
Geniox GO
Diameter of pulley in
mm
Position for DIP switches called 1, 2,
3
Motor
10 77 100 90TYD-S214-M 2.8 Nm
11 77 100
12 95 100
14 95 100
16 118 010 120TYD-S214-M 5.5 Nm
18 112 110
20 118 110
22 118 001
24 132 001
27 140 001
29 150 001
31 160 011 120TYD-S214-L 8 Nm
DV 190 180 011
DV 240 180 011
211728 | v7.2