Geniox GO User manualv7.2

Table Of Contents
|
69
The cabinet contains the speed controller with all components, terminal blocks, LED displaying the operation mode, the
dual position DIP switches with 5 sliding levers for programming the rotor motor signal.
Through the different combinations of the 5 sliding levers of these dual position DIP switches, the correct signal is
available for the 3 different motors used for the 12 sizes of air handling units. The sliding levers are set and the function
is checked at the factory. The positions of the levers appear from the tables below.
7.1.1 Selection of correct signal via the 5 DIP switch levers in NOVA drive 370
Position Function
Code
Up direction ON
Active = ON
1
Down direction numbers
1, 2, 3, 4, 5
Deactivated = OFF
0
The factory sets the positions of the 3 DIP switch levers called 1, 2, 3 for the maximum about 14 revolutions per
minute for standard temperature exchangers. The position of each of the 3 DIP switches called 1, 2, 3 is shown
below.
Geniox GO
Diameter of pulley in
mm
Position for DIP switches called 1, 2,
3
Motor
10 70 000 90TYD-S214-M 2.8 Nm
11 70 000
12 77 000
14 70 100
16 77 100
18 95 100
20 106 010 120TYD-S214-M 5.5 Nm
22 118 010
24 118 010
27 118 110
29 106 001
31 112 001
DV 190 132 011 120TYD-S214-L 8 Nm
DV 240 150 011
The factory sets the positions of the 3 DIP switch levers called 1, 2, 3 for the maximum about 20 revolutions per
minute for sorption-hybrid exchangers as well as for sorption exchangers. The position of each of the 3 DIP switches
called 1, 2, 3 is shown below.
Geniox GO
Diameter of pulley in
mm
Position for DIP switches called 1, 2,
3
Motor
10 77 100 90TYD-S214-M 2.8 Nm
11 77 100
12 95 100
14 95 100
16 118 010 120TYD-S214-M 5.5 Nm
18 112 110
20 118 110
22 118 001
24 132 001
27 140 001
29 150 001
31 160 011 120TYD-S214-L 8 Nm
DV 190 180 011
DV 240 180 011
211728 | v7.2