Geniox GO User manualv7.2

Table Of Contents
20
| Installation
3. Press the sections hard together so that the rubber profiles are so flat that the iron frames of the two sections are
joined. Straps with tensioner are suitable for pressing the sections hard together. Place the strap on the bottom
profiles (pos. A) and pull sections together. When sections are pulled fully together it may be helpful to place the
strap halfway up on the unit (pos. B) to press the sections fully together so that the rubber seals are closing 100%
tight.
Caution
Only gentle tension is allowed on vertical profiles because they are not reinforced for brutal stress in this
direction and profiles may get bent.
Caution
Do not place the strap on the duct connectors !
4. Geniox GO units have clamp locking
system. Ensure that sections are aligned
before trying to pull sections together. If
there is a gap between the two clamps
(fig. A), try pulling the sections further
until both clamps gets fully locked
together and fix them with 8 mm bolts
(fig. B). Bolts are delivered.
J.1.9 Fitting the ductwork
Flexible duct connections between unit and ductwork must always be installed. Be sure that flexible duct connections
are almost fully stretched. (Flexible connections are ordered as accessories and they are packaged placed near the
unit). At the fan outlet on a centrifugal fan, the duct size should be as close to the outlet size as possible. Avoid block-
age and turbulence at the fan outlet.
J.1.10 Risk of stack effect by vertical ducts and wind pressure on louvers
Important
The Systemair air handling units can be ordered and delivered without dampers, and the installer/user must
check that duct systems with the described risk of stack effect (chimney effect) will be provided with
dampers and spring return motors.