Geniox GO User manualv7.2
Table Of Contents
- A Manufacturer
- B Name of machines
- C Declaration of Conformity
- D General descriptions, dangers and warnings
- E The control panel for the control system.
- F Drawings, diagrams, guides and instructions for the use, maintenance and repair
- G Employees in charge of operation/control/maintenance
- H Unintended use and misuse – inappropriate applications for the machine
- I Instructions for unloading and handling on site
- J Installation
- J.1 Installation - mechanical
- J.1.1 Free area in front of and above the unit
- J.1.2 Supporting surface
- J.1.3 Adjustable feet under legs or base frame and transport of sections
- J.1.4 Base frame assembly
- J.1.5 Base frames for outdoor units
- J.1.6 Outdoor units — support under the base frame of the unit
- J.1.7 Installation on the site of unit sections at the base frame when sections are delivered on pallets
- J.1.8 Joining the unit sections
- J.1.9 Fitting the ductwork
- J.1.10 Risk of stack effect by vertical ducts and wind pressure on louvers
- J.1.11 Door alignment
- J.1.12 Lock the doors by using the key
- J.2 Installation - electrical
- J.3 Installation – Pipes for water – hot and chilled, valves and drains
- J.1 Installation - mechanical
- K Installation and assembly instructions for reduction of noise and vibration emissions
- L Start-up, adjustments, use and commissioning
- M Information about the residual risks
- N Instructions on the protective measures during repair and maintenance
- O The essential characteristics of tools which may be fitted to the machinery
- P The conditions of stability during use, transportation, assembly, dismantling when out of service
- Q Instructions for machinery where these are regularly to be transported
- R The operating method to be followed in the event of breakdown. Safe restart.
- S Adjustment and maintenance operations
- T Instructions to enable adjustment and maintenance safely
- U Information on airborne noise emissions exceeding 70 dB(A)
- Annex 1 Technical data – unique data for every unit (in separate cover)
- Annex 2 Assembly of base frame – height 118 mm for unit sizes 10 – 18
- Annex 3 Assembly of base frame – height 118 mm for unit sizes 20 – 27
- Annex 4 Assembly of base frame – height 218 mm for unit sizes 10 – 18
- Annex 5 Assembly of base frame – height 218 mm for unit sizes 20 – 27
- Annex 6 Installation of steel roof in the sizes 10 – 31
- Annex 7 Speed control for rotor and assembly of divided rotor
- Annex 8 Reversible heat pump unit (in separate cover, if heat pump was delivered)
- Annex 9 Menu for internal controller in the heat pump unit (in separate cover, if heat pump was delivered)
- Annex 10 Connection of fan motor and set-up manual for frequency converter
- Annex 11 Commissioning protocol (in separate cover)
- Annex 12 Report with data from final functional test on the Systemair factory
- Annex 13 Short description of main components in the control system
- Annex 14 Wiring diagram (in separate cover)
- Annex 15 Operator’s guide (How to use the Systemair control panel) (in separate cover)
20
| Installation
3. Press the sections hard together so that the rubber profiles are so flat that the iron frames of the two sections are
joined. Straps with tensioner are suitable for pressing the sections hard together. Place the strap on the bottom
profiles (pos. A) and pull sections together. When sections are pulled fully together it may be helpful to place the
strap halfway up on the unit (pos. B) to press the sections fully together so that the rubber seals are closing 100%
tight.
Caution
Only gentle tension is allowed on vertical profiles because they are not reinforced for brutal stress in this
direction and profiles may get bent.
Caution
Do not place the strap on the duct connectors !
4. Geniox GO units have clamp locking
system. Ensure that sections are aligned
before trying to pull sections together. If
there is a gap between the two clamps
(fig. A), try pulling the sections further
until both clamps gets fully locked
together and fix them with 8 mm bolts
(fig. B). Bolts are delivered.
J.1.9 Fitting the ductwork
Flexible duct connections between unit and ductwork must always be installed. Be sure that flexible duct connections
are almost fully stretched. (Flexible connections are ordered as accessories and they are packaged placed near the
unit). At the fan outlet on a centrifugal fan, the duct size should be as close to the outlet size as possible. Avoid block-
age and turbulence at the fan outlet.
J.1.10 Risk of stack effect by vertical ducts and wind pressure on louvers
Important
The Systemair air handling units can be ordered and delivered without dampers, and the installer/user must
check that duct systems with the described risk of stack effect (chimney effect) will be provided with
dampers and spring return motors.
211728 | v7.2