USER MANUAL DV WITHOUT CONTROLLER VERSION 1.01.13 90925371

47
r.3.3Bagfilters
Releasethebagfiltercellsbyactivatingthehandlesandpulloutthefiltercellsoftheunitcasing.Theframe
profilesaretobecleanedandallsealscheckedfordamage.Thehandlesandlockingguiderailsarealsoto
be
checked
toensurethattheycanoperate
unobstructed.
Thenewfilterbagsmustbepushedcarefully
intotheunitinordertoensurethattheyaresealedproperly.Thevariousfiltersizesshouldbeplacedinan
ordercorrespondingtothewayinwhichtheunitisdesigned, andthefiltersmusthaveverticalbags.
r.3.4Panelfilters
The
filtercellguiderailsareto becleanedbeforefittingthenewfilters.
r.4Otherfunctionstomaintain
r.4.1Theunit
Theunitshouldbecleanedonceayearwhenoperatingwithnormalairqualityforcomfort ventilationwith
nospecialhygiener equirements.
To cleantheunit,dryitoffwithadrycloth,orusewatermixedwitha
non
corrosivecleaningmedium.
Anycorr osioni.e.atthefiltersshouldbecleanedoffimmediately,andthesurfacetreated.
Inspecialoperatingconditions,wheretheairis
aggressive
orveryhumid,forexample,orwherethereare
specialhygienerequirements,theunitshallbecleanedmorefrequentlyasr equired.

Cleaning
mediumandmethodshouldbeadapted to the
relevant
conditions.Anycorrosionshouldbe
cleanedoffimmediately,andthesurfacetreated.
Closingmechanismsaretobelubricatedatleastonceayear.Syntheticdoor hingesareservicefree.Seals
aroundinspectiondoorsare
to
becleanedatleastonceayearandaretobecheckedforleakage.
Itisrecommendedtotreatthesealswithamoisturerepellentagent.Connectingpiecesfortheunit
sections,includingtheDiscLocktypes,ar e
to
becheckedfortightnessatleastonceayear.
Allsealsaretobeinspectedatleastonceayearandareto berepairedifnecessary.
Grillesforairintakeandexhaustairoutletareto becleanedatleastonceayearto preventblockage.
