USER MANUAL DV WITHOUT CONTROLLER VERSION 1.01.13 90925371

38
l.7.2.Riskcausedbypermanentmagnetmotor
Hazards/dangerousarea:
Rotationoftheshaftgenerateselectricity.Thisdangerisalwaysvisualizedbyayellowwarninglabelonthe
inspectiondoorwherepermanentmagnetmotorsareinstalled.
Dangerousincident:
Personstouchingconductivepartsgetelectricshock,burns,heartflickerandsoon.
Claimforreductionofdanger:
Byinstallationorrepairsofconductivecomponents,theshaftmustbeblockedtopreventanyrotation.
l.7.3Riskofrotatingimpellercausedbystackeffect(chimneyeffect).
Hazards/dangerousarea:
Onspecialoccasionsstackeffectalsocalledchimneyeffectintheductscreateairflowsthatdrivesthe
impellersbyturnedoffmotors.
Dangerousincident:
Injuryoffingers,handsandarms.
Claimforreductionofdanger:
Eliminatethisairflowforsupplyairandexhaustairbydamperswithspringreturnmotorsforautomatic
closingofthedampersbyturnedofffanmotorsandbypowerfailure.
l.8BatteriesforheatingandcoolingtypeDVRDVHDVKDVU
l.8.1Extremetemperatures‐heating
Hazards/dangerousarea:
Electricalheatingelementscanachievesurfacetemperatureof500degreeCelsius.
Batteriesandpipesforhotwatercanachieve95degreeCelsius.
Dangerousincident:
AccordingtoISO137321:2006,hereisnodirectriskofburns.(shorttimecontactlesserthan2,5sec).
Claimforreductionofdanger:
No.
l.8.2Extremetemperatures‐cooling
Hazards/dangerousarea:
Evaporatorbatteriesandpipesconnectedtocoolingcompressorcanachieveminus10degreesCelsius.
Dangerousincident:
AccordingtoISO137321:2006,hereisnodirectriskofburns.(shorttimecontactlesserthan2,5sec).
Claimforreductionofdanger:
No.
