19
Instructionsforuseofthemachinesectionkinthismanual
Instructionsaboutadjustmentandmaintenancesectionrinthismanual
Safetyduringadjustmentandmaintenancesections
f.Employeesinchargeofoperation/control/maintenance
Afterstartupandhandoverfrominstallertooperators,theunitoperatesfullyautomatically.
IndicationsofoperatingstatusaswellasindicationoffaultsarevisibleinadisplayandonLEDsatahand
terminal.Theoperatorscanenternewparametersinacontrollerviabuttonsonahand
terminal.
Alternatively,thecontrollercanbeconnectedtoaBMSsystemsothatnewparameterscanbeselectedvia
PC,tabletorSmartphone.Theoperatorsdonotneedtoopeninspectionsdoorsfortheoperation
Skilledtechniciansmustcarryoutmaintenanceaswellasrepairs.
g.Intendeduseandrangeofapplications
Theairhandlingunitsareintendedforthetransportandtreatmentofairbetween‐40°Cand+40°C
Theunitsareexclusivelyforcomfortventilation.Theunitsarenotforenvironmentsthatexceedthe
corrosionclassC4accordingtoENISO129442.
Intendedapplicationsfortheunitsare:
Offices,teachingrooms,hotels,shops,homesandsimilarcomfortzones.
h.Unintendeduseandmisuseinappropriateapplicationsforthe
machine
Unitsforoutdoorinstallationmustbespecifiedandorderedforoutdoorinstallation.
TheunitsmustnotbeusedinenvironmentsthatexceedcorrosionclassC4accordingtoENISO129442,
andfortransportofsolidparticles.
Examplesofnotintendeduse:
Kitchenextraction,swimmingpools,offsho re,Exareas,drying
ofwashedclothes.
Donotusetheunitwithpartlyfinishedductsystems.Donotusetheunitforventilationofthebuildingsite
untiltheunitisproperlyprovidedwithguards.
h.1Airhandlingunitinoperation
Thepressuredifferencebetweeninteriorandexterioroftheunitmustnotexceed2000PafortheDV10
anduptoDV150(includingDV150),and1500PaforDV190andDV240.
Beforestartupoftheunitallducts,safetyguardsandallprotectivedevicesmust
bemountedtoprevent
anyaccesstorotatingfanimpellers.Allinspectiondoorsmustbeclosedandlockedwhentheunitisin
operation.
Donotusetheunitwithoutfilters.
