USER MANUAL DV WITHOUT CONTROLLER VERSION 1.01.13 90925371

12—5
12.4SetupDanfossFC101forDVunitswithPMmotors
SETUPISDONEINFACTORYBEFOREDELIVERY
ToreloadSystemairfactorysettingsfromthecontrolpanel:
050:LCPCopy: [2]
SystemairfactorysetupisbasedonDanfossinitialization.
1422:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactorysetup:
001:Languageselection:
106:ClockwiseDirection: [1]Inverse
110:MotorConstruction: [1]PM,nonsalientSPM
124:MotorCurrent: Accordingtomotorplate/Schedule
125:MotorNominalSpeed:Accordingtomotorplate/Schedule
126:MotorCont.Ratedtorque: Accordingtomotorplate/
Schedule
130:StatorResistance(Rs): Accordingtomotorplate/Schedule
137:daxisinductance(Ld): Accordingtomotorplate/Schedule
139:MotorPoles: Accordingtomotorplate/Schedule
140:BackEMFat1000RPM: Accordingtomotorplate/Schedule
142:Motor
CableLength: 3m
173:Flyingstart: [1]Enabled
190:MotorThermalProtection: [2]Thermistortrip
315:Reference1Source: [2]AnaloginputAI54
193:ThermistorSource: [1]AnaloginputAI53
303:MaximumReference: Accordingtomotorplate/Schedule
316+317:Reference2
‐and3Source: [0]Nofunction
341:Ramp1Up: AccordingtoscheduleforPMmotorparameters‐below
342:Ramp1down: AccordingtoscheduleforPMmotorparameters‐below
419:Max.OutputFrequency: Accordingtomotorplate/Schedule
414:MotorSpeedHighLimit: According
tomotorplate/Schedule
512:Terminal27Digitalinput: [0]Nooperation
540.0:FunctionRelay: [3]Driveready/remote
540.1:FunctionRelay: [3]Driveready/remote
625:Terminal54HighReference: Accordingtomotorplate/Schedule
1420:ResetMode: [2]Automaticresetx2
201:
DCbrakecurrent:  100%
202:DCbrakingtime: 20.0sec.
207:Parkingtime: 10,0sec.
050:LCPCopy: [1]AlltoLCP(CopyofSystemairfactorysettingstopanel)
Connections:
010V:Terminal5455andStart:Terminal1218aswellasThermistor: Terminal50
53
Driveready:Terminal12
