USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372
9—5
Connectionofcablestotheterminalsontheboard
Terminal Connection
1 Earth‐supply
2 Earth‐supply
3 Fase
–
supply
4 Neutral
–
supply
5
Rotorturnsupwardsseenfrominspection
side.
Terminal5=wire1
Terminal6=wire2
Terminal7=wire3
Rotorturndownwardsseenfrominspection
side.
Terminal5=wire2
Terminal6=wire1
Terminal7=wire3
6
7
8 Earthforrotormotor
Test
SetDIPswitch4inposition
–
ON
–
andpressthebuttonfortest.Thesignaliscontrolledbythe
potentiometeratconstantspeedandnotbyanysignalfromthecontrol system.
Adjust
IsactivatedbysettingDIPswitch4atOFFandDIPswitch5atON.Herebythemaximum
revolutionscanbeadjustedbetween50and100%bythepotentiometer.Usuallythefactory
settingisOK,butwiththispotentiometerthemaximumrevolutionscanbereducedor
increased.
9 Alarmsignal
–
COM(common)
10 Alarmsignal
–
Relayisnormallyclosed(thisisusedbythecontrolsystemfromSystemair)
11 Alarmsignal
–
Relayisnormallyopen(thisisno
t
usedbythecontrolsystemfromSystemair)
12 Controlsignalinputis0‐10voltDC
13 Controlsignalinput
–
ground
14 Roto rguard
–
(blackcablefromrotorguardfromSystemair)
15 Roto rguard
–
(bluecablefromrotorguardfromSystemair)
16 Roto rguard
–
(browncablefromrotorguardfromSystemair)
17 ForBUSsignal
–
RS485
–
A(greenwirefromSystemaircontrolsystem)
18 ForBUSsignal
–
RS485
–
B(yellowwirefromSystemaircontrolsystem)
19 ForBUSsignal
–
ground(whitewirefromSystemaircontrolsystem)