USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372

61
Ifthereisdustontheedgesofthe
pla
tes,removeitwithasoftbrush.Ifgreaseorothersuchsubstances
arepresent,thentheedgesmustbewashedusinggreasedissolvingdetergents
.
r.5.4.1Bypassdamper
Thedamperbladesarefittedwithsyntheticbearingsrequiringnolubrication.Eachdamperbladeis
connected byapivotingsystem.Thesteelrodsandbrassbushesdo not requirelubrication.Airtightnessof
thedampers,whenthedampermotor isintheclosedposition,must be
visually
checkedonceayear.The
dampermotor istobeadjustedifthedamperdoesnot closetightly.
r.5.4.2Condensatewaterdrain
Onceayearcleanthedriptraybeneaththeheatexchanger,aswellasthedrainandthewater
trap.
Takecarethatthatthereissufficientwaterinthewatertrap.Ifadropleteliminatorhasbeenfitted,this
mustbe
checked
onceayearandcleanedifnecessary.
r.5.5RunaroundheatexchangerDVR
Aheatrecoverysystemofthistypeconsistsofaheatingcoilinthesupplyair‐flowandacoolingcoilinthe
exhaustair‐flow.Afteranextendedrunningperiod(normallyafewyears)
dustparticlescanaccumulateon
thesurfaceofthecoils.Thiscanreducetheefficiencyofthecoils.Cleaningmustbecarriedoutwiththe
utmostcaretoensurethatthecoilfinsarenotdamaged.
Thepipingsystemmustbeventedonceayearasairinthesystemcan
significantlyreducethecapacityof
thecoils.
r.5.5.1Pumpandpressureexpansion
Theserviceinstructionsissuedbythepump manufacturermustbefollowed.Thepressureexpansionsystem
mustbecheckedonceayear.Ifnecessary,thepressuremustbeincreasedto the
cor
rectlevel.
r.5.5.2Condensatewaterdrain
Onceayearcleanthedriptraybeneaththeheatexchanger,aswellasthedrainandthewater
trap.
Takecarethatthatthereissufficientwaterinthewatertrap.Ifadropleteliminatorhasbeenfitted
to
the
coolingcoil,thismustbe
checked
onceayearandcleanedifnecessary.
