USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372
34
i.3.2.1DVunits–labelsonorwiththecabinet
Labelwithdataaboutthecabinet–includingdataaboutfuses–seesectiond.2.2
Flowchart–seesectiond.2.3–uniquefortheorderspecificunit–printedwiththeunique
productionnumberoftheunit
Label
withterminalplanforexternalcomponents–seesectiond.2.5–standard,and notuniquefor
theorderspecificunit
i.3.3Installationofmainspowersupply
AnAC/DCresidualcurrentdevicemustbeinstalledinthepowersupply.Thepowersupplyfortheunitsis
3*400V+N+
PE‐50Hz.Protectionoftheunitsinaccordancewiththelocalstatutoryrequirementsforthe
additionalprotectionofsystemswithfrequencyconvertersandECfans.Theoperatorisresponsibleforthe
installationofthenecessaryprotectionequipment(supplydisconnectingdeviceisnotdeliveredby
Systemair.
i.3.3.1Necessarymainspowersupply
forDVunitswithcabinet/controlsystem
Necessarymainspowersupplyisprintedontheuniquemachinecardplacedonthefrontofeveryunit(see
exampleofamachinecardinsectiond.2.1).
i.3.3.2Necessaryovervoltageprotectiondevice,thatleadslightningovervoltagetoanearthleadona
safeway.
TheInstallerandusermustbeawareofthefactthatlightningstrikesmakeariskthatrequiresinstallation
ofovervoltageprotectiondevicestoleadthelightningovervoltagetoanearthleadinasafeway.
Installerandusermusttakecareofthisaccordingtolocalstatutoryrequirements.
i.3.4Electrical
connectionofcomponentsandfunctions
Externalcomponentsandfunctionsaredeliveredaccordingtotheorderconfirmation.Cablenumbers
appearfromthelabelinsideoronthecabinet,andcablenumbersappearfromthewiringdiagrams.
i.3.4.1ConnectionoftheSystemairControlPaneltotheCorrigoE28controller
TheSCPpanel
isprovidedwith10metresofcable.DemountthecableatthebackoftheSystemairControl
Panel‐pullthecablethroughthecableentryinthecabinet‐andremountthecableinthepanel,oradd
morecable–upto100mofcablebetweentheSystemairControlPanel
andthecontrollerispossible.Place
theSystemairControlPanelontheoutersideoftheunitoronawall.