USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372

30
i.2.7JoiningtheAHUsections
Thesectionsmustbeplacedonthebaseframeandiftheunitisdeliveredwith100mmlegs,thesections
mustbepositioneddirectlyoppositeeachother.
1. Ensurethattheinternalfactoryfittedrubbersealingisundamaged
2. Thesectionsarethentobepositioneddirectlyoppositeeachother.Ifthesectionsarebuiltwith
legs,theadjustablefeetcanbeusedtogetthesectionsparallelandatthesameheight.
3. Pressthesections
hardtogethersothattherubberprofilesaresoflatthattheironframesofthe
twosectionsarejoined.Strapswithtensioneras shownbelowaresuitableforpressingthesections
hardtogether.

4. ThesectionsarethentobelockedpermanentlytogetherwiththeblackplasticcoatedSystemair
DiscLocks.TheDiscLocksaredeliveredinacartonboxplacedinsidetheunit.PlaceeachDiscLock
overthe2factoryfittedlockingpins.Thediscsandlockingpinsarenotreliableforpullingthe
sectionstogether.Theyareonlysufficientforkeepingthesectionswelltogether,sojust
turneach
discgentlywiththesuppliedAllenkey.Useasequencewhereeachdiscistightenedwithonlyone
clickatatime.Iftheunitisplacedtooclosetoawallwithnospaceleftforthemountingof
SystemairDiscLocks,bracketsmustbeplacedinside
theunittokeepthesectionspermanently
together(bracketsforthispurposearenotdeliveredbySystemair)
i.2.8Fittingtheductwork
FlexibleductconnectionsbetweenAHUandductworkmustalwaysbeinstalled.Besurethatflexibleduct
connectionsarealmostfullystretched.(Flexibleconnectionsareorderedasaccessoriesand
theyareplaced
insidetheunit).Atthefanoutletonacentrifugalfan,theductsizeshouldbeasclosetotheoutletsizeas
possible.Avoidblockageandturbulenceatthefanoutlet.
i.2.9Riskofstackeffectbyverticalductsandwindpressureonlouvers
Onspecialoccasionsstackeffectalsocalledchimneyeffectintheductscreateairflowsthatdrivesthe
impellersbyturnedoffmotors.
Arotatingimpellerisapotentialhazardduringcleaningandmaintenanceoftheunit.

Eliminatethisairflowbydamperswithspringreturnmotorsforautomaticclosingofthedampers‐evenby
powerfailure.
Important!TheSystemairairhandlingunitscanbeorderedanddeliveredwithoutdampers,andthe
installer/usermustcheckthatductsystemswiththedescribedriskofstackeffect(chimneyeffect)will
be
providedwithdampersandspringreturnmotors.
