DVU HP brochure uk 06 2015 V3
DVU-HP
Cooling and Heating Capacity, DV 40 with DVU-HP
25 °C /
70% RH
28 °C /
60% RH
31 °C /
50% RH
34 °C /
45% RH
16 16 16 16
49 62 70 86
4,9 7,2 8,5 10,5
10,0 8,6 8,2 8,2
-15 °C /
90% RH
-10 °C /
85% RH
- 5 °C /
80% RH
0 °C /
75% RH
5 °C /
70% RH
Outdoor conditions
22 22 22 22 22 Supply air temperature °C
143 125 103 83 63
Heating capacity kW
Cooling capacity kW
5,2 3,5 3,0 2,6 2,2 Consumed power kW
27,5 35,7 34,3 31,9 28,6 COP, total EER, total
Performance example: DV 40 with
2,5 m
3
/s. Extract 23 °C/63% RH.
Performance example: DV 40 with
2,5 m
3
/s. Extract 22 °C/35% RH.
Defrosting is not taken into account.
20 kW
80 kW
40 kW
30 kW
10 kW
70 kW
50 kW
60 kW
20 kW
80 kW
40 kW
100 kW
30 kW
90 kW
10 kW
70 kW
50 kW
110 kW
60 kW
120 kW
130 kW
Cooling capacity
DVU-HP cooling circuit
Rotary heat exchanger Rotary heat exchanger
DVU-HP heating circuit
Heating capacity
DVU-HP
|
5