DV CONTROL SYSTEM VER. 03.01
0 123456789
A
C
E
G
I
K
Project:
Cre a te Da te : Dra wi ng n o.:
DV Co n tro l syste m - ve r. 0 3 .01 G B
29-09-2017
=FC
Re v Da te .:
DV Control system - Gen 3
In i t.:
30
Sheet:
=FC/31
Ne xt sh ee t:
Total sheets:
36
10 11 12 13 14 15 16 17 18 19
MIKE
Function decription:
B
D
F
H
J
L
A
C
E
G
I
K
B
D
F
H
J
L
0 12345678910 11 12 13 14 15 16 17 18 19
03.00
Version.:
Re v No .:
Set-up Danfoss FC101 for DV-units with AC motors
Connections:
Modbus
Thermistor:
Wire j ump er:
Terminal 61(N) - 68(B) - 69(A)
Terminal 50-53
Terminal 12-19 (no fire)
Systemair factory set-up is based on Danfoss initialisation.
14-22: Operation mode: [2] Initialisation (Danfoss Initialisation)
Systemair factory set-up:
0-01: Language selection:
1-03: T orque characteristic:
1-20: M otor Power:
1-24: M otor Current:
1-25: M otor Nominal Speed:
1-42: Motor Cable Length:
1-50: Motor Magnetisation at zero speed.:
1-52: Min. Speed Normal M agnetisation:
1-73: Flying Start:
1-90: M otor T hermal Protection:
1-93: Thermistor Source:
3-03: M axim um Reference:
3-15: Reference Resource 1:
3-16 + 3-17: Reference 2- and 3 Source:
3-41:Ramp1upanddown:
3-42: Ramp 1 Down time:
4-14: Motor Speed High Limit:
4-19: Max. Output Frequency:
5-10: T erminal 18 Digital Input
5-11: T erminal 19 Digital Input
5-12: T erminal 27 Digital input:
5-40.0: Function Relay:
5-40.1: Function Relay:
6-25: T erminal 54 High Reference:
8-01: Control Site
8-02: Control Source
8-03: Control Timeout T im e
8-04: Control T imeout Function
8-30: Protocol
8-31: Address:
8-32: FC Port Baud Rate
8-33: FC Port Parity
14-20: Reset Mode:
24-00: Fire mode function
24-05: Fire mode Preset Reference
24-09: Fire mode Alarm Handling
0 -5 0: L CP Cop y:
Single fan: [3] Auto-Energy optim.
With twin fan set-up: [1] Variable T orque
According to motor plate / order papers
With twin fan set-up total power must be used
According to motor plate / order papers
With twin fan set-up total current must be used
According to motor plate / order papers
3m
0%
10 Hz
[1 ] E n a b l e d
[2 ] Th e rmi stor tri p
[1] Analog input AI53
Max. Hz from order papers
[11] Local bus reference
[0 ] No fu n cti o n
60 Sec.
30 Sec.
90Hz
90Hz
[0 ] No o p e rati o n
[37] Fire mode
[0 ] No o p e rati o n
[3] Drive ready/rem ote
[3] Drive ready/rem ote
Max. Hz from order papers
[0] Digital and ctrl.word
[1 ] FC P o rt
10 sec.
[2 ] S to p
[2 ] Mo d b u s RTU
1-Supply #1. 3-Supply #2.
2-Extract #1. 4-Extract #2.
[2 ] 9 6 0 0 B a u d
[2 ] No P a rity, 1 stop B i t
[2 ] A u to ma ti c re se t x 2
[1] Enabled run forward
50%
[1] T rip, Critical Alarm s
[1 ] A l l to L CP (Co py of se tti n g s to p an e l )
To store Systemair factory settings from the control panel:
0 -5 0: L CP Cop y: [2 ] A ll fro m L CP
Set-up Danfoss FC101 for DV-units with PM motors
Connections:
Systemair factory set-up is based on Danfoss initialisation.
14-22: Operation mode: [2] Initialisation (Danfoss Initialisation)
Systemair factory set-up:
0-01: Language selection:
1 -0 6 : Cl o ckwi se Di re cti o n :
1-10: M otor Construction:
1-24: M otor Current:
1-25: M otor Nominal Speed:
1-26: Motor Cont. Rated torque:
1-30: Stator Resistance (Rs):
1-37: d-axis inductance (Ld):
1-39: Motor Poles:
1-40: Back EMF at 1000 RPM:
1-42: Motor Cable Length:
1-73: Flying start
1-90: Motor Thermal Protection:
1-93: Thermistor Source:
2-01: DC brake Current:
2-02: DC braking T ime:
2-07: Parking time:
3-03: Maxim um Reference:
3-15: Reference Resource 1:
3-16 + 3-17: Reference 2- and 3 Source:
3-41:Ramp1UpTime:
3-42:Ramp1DownTime:
4-14: Motor Speed High Limit:
4-19: Max. Output Frequency:
5-10: T erminal 18 Digital Input
5-11: T erminal 19 Digital Input
5-12: T erminal 27 Digital input:
5-40.0: Function Relay:
5-40.1: Function Relay:
6-25: T erminal 54 High Reference:
8-01: Control Site
8-02: Control Source
8-03: Control Timeout T im e
8-04: Control Timeout Function
8-30: Protocol
8-31: Address:
8-32: FC Port Baud Rate
8-33: FC Port Parity
14-20: Reset Mode:
24-00: Fire m ode func tion
24-05: Fire m ode Preset Reference
24-09: Fire mode Alarm Handling
0-50: LCP Copy:
[1 ] In ve rse
[1] PM, non salient SPM
According to motor plate / Schedule
According to motor plate / Schedule
According to motor plate / Schedule
According to motor plate / Schedule
According to motor plate / Schedule
According to motor plate / Schedule
According to motor plate / Schedule
3m
[1] Enabled
[2 ] Th e rmi stor tri p
[1] Analog input AI53
100 %
20.0 Sec.
10.0 Sec.
According to motor plate / Schedule
[11] Local bus reference
[0 ] No fu n cti o n
A cco rd i n g to P M S ch e d u le
A cco rd i n g to P M S ch e d u le
According to motor plate / Schedule
According to motor plate / Schedule
[0 ] No o p e rati o n
[37] Fire mode
[0 ] No o p e rati o n
[3] Drive ready/ rem ote
[3] Drive ready/ rem ote
According to motor plate / Schedule
[0] Digital and ctrl.word
[1 ] FC P o rt
10 sec.
[2 ] S to p
[2 ] Mo d b u s RTU
1-Supply #1. 3-Supply #2.
2-Extract #1. 4-Extract #2.
[2 ] 9 6 0 0 B a u d
[2 ] No P a rity, 1 stop B i t
[2] Automatic reset x 2
[1] Enabled run forward
50%
[1] T rip, Critical Alarm s
[1 ] A l l to L CP (Co py of se tti n g s to p a n el )
To store Systemai r factory setti ngs from the control panel :
0-50: LCP Copy: [2] All from LCP
Modbus
Thermistor:
Wire j ump er:
Terminal 61(N) - 68(B) - 69(A)
Terminal 50-53
Terminal 12-19 (no fire)