AirHumidifiers 01 2015 V2

with two heating coils
DV Air handling unit
The evaporative process into the Mollier chart
The illustration on page 7 shows an example of the usual
design process for humidification into the Mollier chart
with 2 heating coils (pre- and post heating): Starting from
outside air at –3 °C and 40% RH to achieve air at 22 ºC
and 50% RH.
Pre-heating + humidification + post heating
See illustration with 1-2-3-4 on page 7.
This example has absolute humidity increase from
1.5 g/kg to 8 g/kg.
With two heating coils you can accept a lower starting
temperature before the humidification. The reason is that
if the air temperature is lower after the humidification
than desired, you have the possibility to heat up the air in
order to end up with the desired air conditions.
1. The air is heated up from -3 ºC and 40% RH through
the rotary heat exchanger and furthermore through the
pre-heating coil until the desired temperature is
reached.
2.
Now the air has a RH of 4% and a temperature of 34 °C.
As the air passes through the humidifier, the saturated
pads of the humidifier pass on the moisture to the air.
This changes both the humidity of the air as well at the
temperature.
3. Ending with 17
°C
and 70% RH by following the
enthalpy lines in the Mollier chart.
4. After passing through the post heating coil the tempe-
rature rises to the end conditions of 22
°C
and 50% RH.
How to choose in SystemairCAD
If this is the chosen solution you may have to change the
CelPad thickness of the HU-CELL material. You will also
have the possibility to change the starting temperature to
reach your desired leaving air conditions. Here you will
have the possibility not only to change the humidifier
thickness but also the temperatures. This solution ensures
you more possibilities. However, it is also more demand-
ing for the control system. The selection can be made in
the SystemairCAD and calculated instantly to find the
leaving air conditions of the AHU.