AirHumidifiers 01 2015 V2
with single heating coil
DV Air handling unit
DV Air handling unit with single heating coil
The performance control can be achieved by an ON-OFF
hygrostat acting on the pump motor contactor.
The evaporative process into the Mollier chart
The illustration on page 5 shows an example of the usual
design process for humidification into the Mollier chart:
Starting from outside air at -3 ºC and 40% RH to achieve
air at 22 ºC and 50% RH.
Single heating coil + humidification
See illustration with 1-2-3 on page 5.
This example has absolute humidity increase
from 1.5 g/kg to 8 g/kg.
With a single heating coil you will need to heat up the air
to a high starting temperature before the humidification.
This will allow you to end up with the desired air condi-
tions.
1. The air is heated up from -3
°
C and 40% RH through
the rotary heat exchanger and furthermore through the
heating coil until the desired temperature is reached.
2.
Now the air has a RH of 3% and a temperature of 40 °C.
As the air passes through the humidifier, the saturated
pads of the humidifier pass on the moisture to the air.
This changes both the humidity of the air as well as the
temperature.
3. Ending with 22 °C and 50% RH by following the
enthalpy lines in the Mollier chart.
How to choose in SystemairCAD
When choosing the design with one heating coil, it can be
difficult to reach 100% accurate end temperature and
humidity. If this is the chosen solution you may have to
change the CelPad thickness of the HU-CELL material. This
will always be a balance of choosing the correct
humidifier thickness and the correct starting temperature
before humidification. The selection can be made in the
SystemairCAD and calculated instantly to find the leaving
air conditions of the AHU.
| Air Humidifiers