Model 810 900 980 1060 1160 1260
Nominal cooling capacity
1
kW 768,3 884,2 971,2 1035,1 1139,2 1222,6
Inputpower
1
kW 248,4 285,6 316,3 325,1 363,4 403,9
EER
1
/EnergyEfciencyClass 3,09/B 3,10/A 3,07/B 3,18/A 3,13/A 3,03/B
EER
CONDITIONB
(74%) 3,98 3,91 4,13 4,25 4,25 4,29
EER
CONDITIONC
(47%) 5,09 5,06 5,11 5,33 5,35 5,41
EER
CONDITIOND
(21%) 6,97 6,71 6,52 7,12 7,31 7,17
SEER
2
4,84 4,79 4,85 5,08 5,10 5,09
η
s,c
2
% 191 189 191 200 201 201
Number of refrigerant circuits 2
Total capacity steps
*
% 13%÷100% 14%÷100% 13%÷100% 17%÷100% 15%÷100% 14%÷100%
Compressor
Number 2
Type 1variablespeed+1xedspeed
N°of loading stages Continuous capacity control
Evaporator
Number 1
Type Shell & tube
Waterow m
3
/h 132,5 152,3 167,4 178,4 196,4 210,8
Pressure drop kPa 36 20 23 26 32 32
Water volume l 276 379 367 356 356 431
Antifreeze Heater W 300 300 300 300 300 300
Air cooled condenser
Number of coils 16 18 20 22 24 24
Total coil face area per coil m
2
2,3
Fans
Number of fans 16 18 20 22 24 24
Nominal speed rpm 800 800 800 800 800 800
Totalairow m
3
/h 367.920 414.000 460.080 506.160 552.240 552.240
Total input power kW 16,0 18,0 20,0 22,0 24,0 24,0
Water Connections (Evaporator)
Type Victaulic
InletDiameter inch 8 8 10 10 10 10
Outlet Diameter inch 8 8 10 10 10 10
Water Connections (Desuperheater)
Type Male GAS Threaded
InletDiameter inch 2” 2” 2” 2” 2” 2”
Outlet Diameter inch 2” 2” 2” 2” 2” 2”
Weight
Shipping kg 6.341 7.033 7.485 8.212 8.596 8.731
Operating kg 6.617 7.412 7.852 8.579 8.963 9.162
Additional weight
Desuperheater versions kg 147 147 180 180 216 216
Dimensions
Length mm 8.868 9.920 10.972 12.024 13.076 13.076
Width mm 2.192 2.192 2.192 2.192 2.192 2.192
Height mm 2.590 2.590 2.590 2.590 2.590 2.590
Acoustic Data
Sound power level
3
dB(A) 98 99 99 99 100 100
Sound pressure level at 10 m
4
dB(A) 65 66 66 66 67 67
1
Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2
According to commission regulation (EU) N° 2281/2016 for comfort chillers
3
Soundlevelsareatfullyloadedconditions.SoundpowerlevelvaluesrefertoISOstandard3744.
4
SoundpressurelevelsrefertoISOStandard3744,parallelepipedshape.
*
This value can change for BC version or other special applications