Technical Data - SYSCREW AIR EVO HSE S R134a
Model 380 440 510 590 660 730
Nominal cooling capacity
1
kW 359,2 437,4 493,3 557,5 633,7 695,6
Inputpower
1
kW 122,2 140,4 162,8 178,4 202,8 224,4
EER
1
/EnergyEfciencyClass 2,94/B 3,12/A 3,03/B 3,13/A 3,12/A 3,10/A
EER
CONDITIONB
(74%) 4,00 4,11 4,08 4,10 4,05 4,07
EER
CONDITIONC
(47%) 4,81 5,18 5,18 5,32 5,04 5,01
EER
CONDITIOND
(21%) 6,54 6,93 6,86 7,04 7,01 6,76
SEER
2
4,66 4,92 4,90 5,00 4,87 4,82
η
s,c
2
% 184 194 193 197 192 190
Number of refrigerant circuits 2
Total capacity steps
*
% 22%÷100% 18%÷100% 16%÷100% 14%÷100% 13%÷100% 15%÷100%
Compressor
Number 2
Type 1variablespeed+1xedspeed
N°of loading stages Continuous capacity control
Evaporator
Number 1
Type Shell & tube
Waterow m
3
/h 61,9 75,4 85,0 96,1 109,3 119,9
Pressure drop kPa 16 24 18 23 30 29
Water volume l 149 142 246 246 228 276
Antifreeze Heater W 200 200 300 300 300 300
Air cooled condenser
Number of coils 8 10 10 12 14 14
Total coil face area per coil m
2
2,3
Fans
Number of fans 8 10 10 12 14 14
Nominal speed rpm 800 800 800 800 800 800
Totalairow m
3
/h 183.960 230.040 230.040 276.120 321.840 321.840
Total input power kW 8,0 10,0 10,0 12,0 14,0 14,0
Water Connections (Evaporator)
Type Victaulic
InletDiameter inch 6 6 8 8 8 8
Outlet Diameter inch 6 6 8 8 8 8
Water Connections (Desuperheater)
Type Male GAS Threaded
InletDiameter inch 2” 2” 2” 2” 2” 2”
Outlet Diameter inch 2” 2” 2” 2” 2” 2”
Weight
Shipping kg 3.832 4.210 4.744 5.077 5.474 6.017
Operating kg 3.981 4.352 4.990 5.323 5.702 6.293
Additional weight
Desuperheater versions kg 76 86 100 100 114 114
Dimensions
Length mm 4.660 5.712 5.712 6.764 7.816 7.816
Width mm 2.192 2.192 2.192 2.192 2.192 2.192
Height mm 2.590 2.590 2.590 2.590 2.590 2.590
Acoustic Data
Sound power level
3
dB(A) 94 94 97 97 97 98
Sound pressure level at 10 m
4
dB(A) 62 62 65 65 65 65
1
Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2
According to commission regulation (EU) N° 2281/2016 for comfort chillers
3
Soundlevelsareatfullyloadedconditions.SoundpowerlevelvaluesrefertoISOstandard3744.
4
SoundpressurelevelsrefertoISOStandard3744,parallelepipedshape.
*
This value can change for BC version or other special applications