EDM SYSCREW AIR EVO HSE

|
SYSCREW 380-1260 AIR EVO HSE
15
Operating Limits
SYSCREW 380-1260 AIR EVO HSE
380 450 510 590
Min Max Min Max Min Max Min Max
Chilled
liquid
Leaving water
temperature
Water
°C
from +5 to +15
Brine (brine application)
1
°C
from -8 to 0
Brine (std application)
2
°C from 0 to +5
Temperature spread
K
from +8 to +3
Flow rate
3
mc/h
39 105 48 127 54 144 61 163
Pressure drop
3
kPa 7 48 9 67 7 51 9 66
Maximum operating pressure
bar
10
Ambient
Air entering
temperature
Cooling
°C
from -10 to +46
Cooling (S) °C from -10 to +44
Cooling (HT)
°C
from-10to+49
Minimum ext. air
°C
-10 -10 -10 -10
External
static pressure
Standard fans Pa 0
High pressure fans
Pa
< 120
Recommended system chilled water volume
4
l
2.345 2.345 2.345 2.345
Minimum capacity step % 22 18 16 14
Power supply voltage V
400 V+/-10%, 3 Ø, 50 Hz (nominal)*
1
Dedicated evaporator (BC unit) and additional devices.
2
Standard evaporator (CO/TR unit).
3
Totalunitowrateandpressuredroparegivenforstandardevaporator(CO/TRunit).
4
Minimum water contents at normal air conditioning applications.
*Voltagesupplytolerances:+/-10%ofthenominalVoltage(400V)forshorttermapplication;+/-5%ofthenominalVoltage(400V)forcontinuousapplication
SYSCREW 380-1260 AIR EVO HSE
660 730 810 900
Min Max Min Max Min Max Min Max
Chilled
liquid
Leaving water
temperature
Water
°C
from +5 to +15
Brine (brine application)
1
°C from -8 to 0
Brine (std application)
2
°C
from 0 to +5
Temperature spread
K
from +8 to +3
Flow rate
3
mc/h 69 185 76 202 84 224 97 258
Pressure drop
3
kPa
12 85 12 82 14 100 8 58
Maximum operating pressure
bar
10
Ambient
Air entering
temperature
Cooling °C from -10 to +46
Cooling (S)
°C
from -10 to +44
Cooling (HT)
°C
from-10to+49
Minimum ext. air
°C
-10 -10 -10 -10
External
static pressure
Standard fans
Pa
0
High pressure fans
Pa
< 120
Recommended system chilled water volume
4
l
2.345 3.040 3.040 3.659
Minimum capacity step
%
13 15 13 14
Power supply voltage V
400 V+/-10%, 3 Ø, 50 Hz (nominal)*
SYSCREW 380-1260 AIR EVO HSE
980 1060 1160 1260
Min Max Min Max Min Max Min Max
Chilled
liquid
Leaving water
temperature
Water °C from +5 to +15
Brine (brine application)
1
°C
from -8 to 0
Brine (std application)
2
°C
from 0 to +5
Temperature spread K from +8 to +3
Flow rate
3
mc/h
106 282 113 301 124 332 134 356
Pressure drop
3
kPa
9 66 11 77 13 93 13 92
Maximum operating pressure bar 10
Ambient
Air entering
temperature
Cooling
°C
from -10 to +46
Cooling (S)
°C
from -10 to +44
Cooling (HT)
°C
from-10to+49
Minimum ext. air
°C
-10 -10 -10 -10
External
static pressure
Standard fans
Pa
0
High pressure fans
Pa
< 120
Recommended system chilled water volume
4
l
3.659 4.078 4.078 4.078
Minimum capacity step
%
13 14 12 11
Power supply voltage
V
400 V+/-10%, 3 Ø, 50 Hz (nominal)*