Correction Factors
EVAPORATOR CONDENSER
Fouling factor
(m
2
.°C/kW)
Cooling capacity
factor
Power input
factor
Fouling factor
(m
2
.°C/kW)
Cooling capacity
factor
Power input
factor
0,044 1,000 1,000 0,044 1,000 1,000
0,088 0,987 0,995 0,088 0,987 1,023
0,176 0,964 0,985 0,176 0,955 1,068
0,352 0,915 0,962 0,352 0,910 1,135
Fouling factors
Altitude (m) Cooling capacity factor Power input factor
0 1,000 1,000
600 0,987 1,010
1.200 0,973 1,020
1.800 0,958 1,029
2.400 0,943 1,038
Altitude factors
System Water Volume
The minimum system water volume is calculated using the following formula:
V
min
= Cap x MinCapStep x 28,8
Where Cap:NominalUnitCapacity[kW]atconditionsofinstallation
MinCapStep:Minimumunitcapacitystep[%]showninTable7
Iftheapplicationisaprocesscoolingtype,theminimumsystemchilledwatervolumeisgenerallyhigherthanabove
recommended.