EDM SYSCREW AIR EVO HSE

|
SYSCREW 380-1260 AIR EVO HSE
11
Refrigerant Flow Diagram SYSCREW AIR EVO HSE
Sizes 1260 CO
COMPONENTS
1A Compressor (Screw Step type)
1B Compressor(ScrewInvertertype)
2 Air cooled condenser
3 Filter drier
4 Electronic expansion valve
5 Globe valve
6 Heat exchanger (Shell & Tube Type)
7 Desuperheater (Optional)
8 Muffler (Optional)
9 Anti-vibrationpipe(Optional)
10 Solenoid valve (ECO)
11 Thermostatic expansion valve (ECO)
12 Heat exchanger (Phetype) (ECO)
13 Non return valve (ECO)
14 Sight glass (ECO)
15 Suction compressor valve (Optional)
16 Suction accumulator (only BC version)
1A
CIRCUIT 1
STEP+ECO
AF
H
G
D
5
BT
B
16
S
S
15
55
A
7
9
8
A
AT
M
5
2
6
EEV
CONTROL
UNIT
CONTROL
3
10
11
13
12
14
CIRCUIT 2
INVERTER+ECO
E
F
8
9
M
S
5
AT
A
A
7
G
2
D
1B
L
AF
5
16
B
BT
13
5
10
14
11
UNIT
CONTROL
EEV
CONTROL
3
S
15
12
4
SAFETY/CONTROL DEVICES
A High pressure switch
AT High pressure transducer
B Low pressure switch
BT Low pressure transducer
S 5/16”Shraderconnection
D Air temperature sensor
E Outlet water temperature sensor
F Inletwatertemperaturesensor
G PED pressure relief valve HP side
H PED pressure relief valve LP side
M Discharge temperature sensor
AF AccessfittingSAEFLARE3/8”
L Oil level switch
↓ PressurePipeconnectionwithShradervalve