10 - Troubleshooting (continued)
S.NO.
WARNING /
ALARM NO.
DESCRIPTION TROUBLESHOOTING
11 A14 Ground fault
Remove power to the frequency converter and repair the ground fault.
Check for ground faults in the motor by measuring the resistance to ground of the motor
cables and the motor with a megohmmeter.
Reset any potential individual offset in the 3 current transducers in . Perform the manual
initialisation or perform a complete AMA. This
method is most relevant after changing the power card.
12 A29 Drive over temperature
Check for the following conditions.
The ambient temperature is too high.
The motor cables are too long.
Incorrect airflow clearance above and below the frequency converter.
Blocked airflow around the frequency converter.
Damaged heat sink fan.
Dirty heat sink.
13 A30 Motor phase U missing
Remove the power from the frequency converter and check motor phase U.
14 A31 Motor phase V missing Remove the power from the frequency converter and check motor phase V.
15 A32 Motor phase W missing Remove the power from the frequency converter and check motor phase W.
16 A47 24 V supply low Check for a defective power card.
17 A65
Control Board Over-
temperature
Check that the ambient operating temperature is within the limits.
Check for clogged filters.
Check the fan operation.
Check the control card.
18 A244 Heatsink temp
19 A16 Short Circuit Remove the power to the frequency converter and repair the short circuit.
20 A33 Inrush fault Let the unit cool to operating temperature
21 A38 Internal fault
Cycle power.
Check that the option is properly installed
Check for loose or missing wiring
22 A45 Earth fault 2
Check for proper grounding and loose connections.
Check for proper wire size.
Check the motor cables for short circuits or leakage currents.
23 A46 Pwr. card supply
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC supply is used, verify proper supply power."
24 A48 1.8 V supply low
Check for a defective control card.
If an option card is present, check for overvoltage.
25 A69 Pwr. Card Temp
Check that the ambient operating temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the power card.