IOM SYSCREW AIR EVO HSE

22
6 - Control
6.1 General information
Introduction
This document contains the information and the operating instructions
for 2 screw compressors (step type and inverter driven type).
This information is for the after-sales service and the production
operators, for the end-of-line testing.
Main characteristics
Microprocessor control
User-friendly keyboard
Proportional and integral control of the return water temperature
or leaving water temperature (LWT or RWT)
Access code to enter the Service Level
Access code to enter User Level
Basic functions without access code
Alarm and LED
Backlighted LCD
Rotation of the compressor operation
Oil return function - Standard for the inverter compressor,
optional (oil switch device) for step compressor
Night mode (or Low Noise) control
Counting of the pump/compressors’ hours of operation
Display of discharge and suction pressure values
Display of temperature sensor
History of stored alarms (option)
Built-in serial communication RS485 port with Modbus protocol
to connect the main board to a BMS network.
This built-in port is available as standard only in the case no
extra network control systems (netTune) are selected with the
units.
Built-in serial communication Ethernet port with two possible
protocols (Modbus or Bacnet, in case also at the same time). In
case of Bacnet communication protocol it is needed to activate a
license.
Custom protocols are available on request
The following accessories can be also connected:
Remote Display Terminal.
The control system consists of:
a) Main Board. The units are provided with a microprocessor card
which is fully programmed by default for the control of a chiller
of cold only type with 2 circuits, 1 compressor for circuit, a HP
transducer and a LP transducer for Circuit.
b) EEV controllers (two separate drivers) for the management of the
electronic expansion valves.
C) Keyboard & Display Terminal.
The terminal makes it possible to carry out the following operations:
– the change of the main operating parameters
– the display of the detected alarms
– the display of all the measured quantities
The terminal and the card are connected by a 6-way phone cable.
The connection of the terminal to the basic card is not essential for
the normal operation of the controller.