EDM SYSCREW AIR EVO HSE

SYSCREW 380-1260 AIR EVO HSE
|
48
Low head pump/s - S R134a [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 164% 172% 61.594 218 32 186 5,5 10,4
440 175% 183% 75.033 196 47 149 5,5 10,4
510 169% 179% 84.581 210 48 161 7,5 14,1
590 174% 181% 95.624 198 62 136 7,5 14,1
660 168% 180% 108.735 230 79 150 9,2 17,4
730 165% 183% 119.336 231 89 142 11,0 20,2
810 169% 180% 131.859 215 71 144 11,0 20,2
900 161% 181% 153.084 223 68 154 15,0 26,6
980 161% 183% 166.949 216 80 136 15,0 26,6
1060 165% 182% 176.673 257 90 167 18,5 32,7
1160 169% 185% 194.500 247 108 138 18,5 32,7
1260 166% 182% 208.735 283 120 164 22,0 42,2
High head pump/s - S R134a [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 156% 169% 61.594 268 32 235 7,5 13,6
440 166% 179% 75.033 295 47 248 9,2 17,2
510 169% 179% 84.581 279 48 231 9,2 17,2
590 168% 179% 95.624 304 62 242 11,0 20,2
660 163% 180% 108.735 296 79 216 15,0 26,6
730 161% 179% 120.792 335 91 244 18,5 32,7
810 161% 181% 133.789 324 73 251 18,5 32,7
900 161% 181% 153.084 313 68 244 22,0 42,2
980 161% 182% 168.980 306 82 224 22,0 42,2
1060 162% 179% 176.673 302 89 213 22,0 42,2
1160 161% 184% 195.930 383 110 273 30,0 53,5
1260 161% 182% 209.759 376 121 255 30,0 53,5
Low head pump/s - S R513A [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 171% 180% 62.838 216 34 183 5,5 10,4
440 182% 192% 76.549 193 49 144 5,5 10,4
510 175% 184% 86.289 208 50 158 7,5 14,1
590 180% 190% 97.555 195 64 131 7,5 14,1
660 174% 187% 110.931 227 83 144 9,2 17,4
730 172% 184% 122.044 228 93 135 11,0 20,2
810 176% 188% 134.523 211 74 137 11,0 20,2
900 165% 185% 155.045 222 70 152 15,0 26,6
980 167% 186% 169.908 215 83 132 15,0 26,6
1060 172% 186% 180.242 255 93 162 18,5 32,7
1160 175% 192% 198.429 244 113 132 18,5 32,7
1260 172% 191% 212.952 280 125 156 22,0 42,2
High head pump/s - S R513A [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 163% 179% 62.838 266 34 232 7,5 13,6
440 173% 180% 76.549 293 49 244 9,2 17,2
510 176% 182% 86.289 276 50 226 9,2 17,2
590 175% 184% 97.555 303 64 239 11,0 20,2
660 170% 179% 110.931 294 83 211 15,0 26,6
730 165% 179% 122.044 334 93 241 18,5 32,7
810 163% 182% 134.523 323 74 249 18,5 32,7
900 165% 182% 155.045 312 70 242 22,0 42,2
980 162% 184% 169.908 306 83 223 22,0 42,2
1060 168% 184% 180.242 301 93 208 22,0 42,2
1160 165% 180% 198.429 382 113 269 30,0 53,5
1260 166% 179% 212.952 374 125 249 30,0 53,5
SYSCREW 380-1260 AIR EVO HSE S R134a
SYSCREW 380-1260 AIR EVO HSE S R513A
*
Pump with inverter mandatory