EDM SYSCREW AIR EVO HSE
|
SYSCREW 380-1260 AIR EVO HSE
47
Hydro options
Low head pump/s - STD / HT R134a [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 169% 177% 62.083 218 33 185 5,5 10,4
440 176% 184% 75.238 195 47 148 5,5 10,4
510 170% 179% 84.912 209 49 160 7,5 14,1
590 175% 184% 96.077 197 62 135 7,5 14,1
660 170% 179% 109.321 229 80 149 9,2 17,4
730 168% 179% 120.516 230 91 139 11,0 20,2
810 170% 181% 132.226 214 71 143 11,0 20,2
900 161% 179% 153.375 223 69 154 15,0 26,6
980 161% 182% 166.991 216 80 136 15,0 26,6
1060 165% 179% 177.008 257 90 167 18,5 32,7
1160 168% 181% 195.082 247 109 137 18,5 32,7
1260 165% 182% 209.694 283 121 162 22,0 42,2
High head pump/s - STD / HT R134a [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 161% 174% 62.083 267 33 234 7,5 13,6
440 167% 179% 75.238 295 47 248 9,2 17,2
510 170% 179% 84.912 279 49 230 9,2 17,2
590 170% 179% 96.077 304 62 242 11,0 20,2
660 166% 179% 109.321 295 80 215 15,0 26,6
730 161% 179% 120.399 336 90 245 18,5 32,7
810 161% 179% 133.838 324 73 251 18,5 32,7
900 161% 179% 153.375 312 69 244 22,0 42,2
980 161% 180% 169.190 306 82 224 22,0 42,2
1060 162% 180% 177.008 302 90 212 22,0 42,2
1160 161% 181% 197.186 383 111 271 30,0 53,5
1260 161% 180% 211.236 375 123 252 30,0 53,5
Low head pump/s - STD / HT R513A [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 163% 170% 62.704 217 34 183 5,5 10,4
440 170% 179% 76.176 194 49 145 5,5 10,4
510 165% 183% 86.179 208 50 158 7,5 14,1
590 169% 187% 97.038 196 64 132 7,5 14,1
660 167% 181% 111.222 227 83 144 9,2 17,4
730 166% 183% 123.195 226 95 132 11,0 20,2
810 167% 184% 135.177 210 74 136 11,0 20,2
900 161% 181% 156.409 221 71 150 15,0 26,6
980 161% 182% 170.717 215 84 131 15,0 26,6
1060 161% 184% 178.778 256 92 164 18,5 32,7
1160 162% 180% 197.033 245 111 134 18,5 32,7
1260 161% 180% 211.791 281 123 158 22,0 42,2
High head pump/s - STD / HT R513A [50 Hz]
Chiller
model
ηs,c - ERP 2018 ηs,c - ERP 2021 Q
nom
H
pump
Δp
circuit
H Pmax F.L.A
FW/VO VW/VO(*) l/h kPa kPa kPa kW A
380 156% 168% 62.704 266 34 233 7,5 13,6
440 162% 179% 76.176 293 49 245 9,2 17,2
510 166% 182% 86.179 276 50 226 9,2 17,2
590 164% 185% 97.038 303 64 240 11,0 20,2
660 163% 179% 111.222 294 83 211 15,0 26,6
730 161% 180% 123.195 333 95 239 18,5 32,7
810 161% 179% 136.154 322 75 246 18,5 32,7
900 161% 180% 156.560 311 72 240 22,0 42,2
980 161% 182% 172.774 304 86 218 22,0 42,2
1060 161% 179% 178.778 301 92 210 22,0 42,2
1160 161% 179% 198.964 382 113 268 30,0 53,5
1260 161% 179% 213.556 373 125 248 30,0 53,5
SYSCREW 380-1260 AIR EVO HSE R134a (STD/HT)
SYSCREW 380-1260 AIR EVO HSE R513A (STD/HT)
*
Pump with inverter mandatory