Brochure SYSCREW 380 1260 AIR EVO HSE 1GB
Model 810 900 980 1060 1160 1260
Nominal cooling capacity
1
kW 778,1 896,9 983,5 1047,4 1154,0 1240,5
Input power
1
kW 253,4 290,2 322,3 332,0 370,4 408,1
EER
1
/ Energy Efciency Class 3,07/B 3,09/B 3,05/B 3,15/A 3,12/A 3,04/B
EER
CONDITION B
(74%) 3,89 3,82 3,98 4,10 4,14 4,20
EER
CONDITION C
(47%) 4,72 4,68 4,72 5,10 5,06 5,02
EER
CONDITION D
(21%) 6,62 6,32 6,22 6,69 6,70 6,68
SEER
2
4,62 4,56 4,60 4,87 4,86 4,85
η
s,c
2
% 182 179 181 192 191 191
Number of refrigerant circuits 2
Total capacity steps
*
% 13%÷100% 14%÷100% 13%÷100% 17%÷100% 15%÷100% 14%÷100%
Compressor
Number/ Type 2 / 1 variable speed + 1 xed speed
N° of loading stages Continuous capacity control
Evaporator
Number/ Type 1/Shell&Tube
Water ow m
3
/h 134,2 154,5 169,5 180,5 199,0 213,9
Pressure drop kPa 36 21 24 27 33 32
Water volume l 276 379 367 356 356 431
Antifreeze Heater W 300 300 300 300 300 300
Air cooled condenser
Number of coils 16 18 20 22 24 24
Total coil face area per coil m
2
2,3
Fans
Number of fans 16 18 20 22 24 24
Nominal speed rpm 900 900 900 900 900 900
Total airow m
3
/h 367.920 414.000 460.080 506.160 552.240 552.240
Total input power kW 24,0 27,0 30,0 33,0 36,0 36,0
Total input power
**
kW 41,0 46,1 51,2 56,3 61,4 61,4
Total input power
***
kW 48,0 54,0 60,0 66,0 72,0 72,0
External static pressure
***
Pa 0 - 120 Pa
Water Connections (Evaporator)
Type Victaulic
Inlet Diameter/Outlet Diameter inch 8/8 8/8 10/10 10/10 10/10 10/10
Water Connections (Desuperheater)
Type Male GAS Threaded
Inlet Diameter/Outlet Diameter inch 2”/2” 2”/2” 2”/2” 2”/2” 2”/2” 2”/2”
Weight
Shipping kg 6.255 6.947 7.397 8.124 8.508 8.643
Operating kg 6.531 7.326 7.764 8.491 8.875 9.074
Additional weight
Desuperheater versions kg 147 147 180 180 216 216
Dimensions
Length mm 8.868 9.920 10.972 12024 13.076 13.076
Width mm 2.192 2.192 2.192 2.192 2.192 2.192
Height mm 2.510 2.510 2.510 2.510 2.510 2.510
Acoustic Data
Sound power level
3
dB(A) 101 102 102 103 103 103
Sound power level
3**/***
dB(A) 105 106 106 107 108 108
Sound pressure level at 10 m
4
dB(A) 68 69 69 70 70 70
Sound pressure level at 10 m
4**/***
dB(A) 72 73 73 74 75 75
SYSCREW AIR EVO HSE R513A (STD/HT/HPF)
Technical Data
systemair 6
1
Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard
2
According to commission regulation (EU) N° 2281/2016 for comfort chillers
3
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744
4
Sound pressure levels refer to ISO Standard 3744, parallelepiped shape
*
This value can change for BC version or other special applications
**
High Temperature Units (HT), data with fans at max speed (1100 Rpm)
***
HPF Units, data with fans at max speed (1100 Rpm)