IOM SYSCREW AIR EVO HSE

74
8 - Technical Data (continued)
8.7 Space requirements
2 mt
2 mt
2 mt
2 mt
FREE SPACE
3,3 mt
2 mt
The units are air-cooled and are designed for outdoor application.
Adequate space around chillers is mandatory, as shown in the pictures below
- to guarantee the proper air flow through the condenser coils, since warm air
recirculation and coil starvation may cause the degradation of performances
or, in the worst cases, the unit shutdown for high pressure.
- to guarantee access for periodic service and maintenance.
These recommendations and are generally enough even in case of
extraordinary maintenance, as the replacement of major components of the
unit (evaporator, compressors, etc).
In any case, to have confirm of the adequate space for this purpose, please
contact your nearest Systemair Sales Office.