IOM SYSCREW AIR EVO HSE
48
8 - Technical Data (continued)
SYSCREW AIR EVO HSE S 810 900 980 1060 1160 1260
Power supply* V/Ph/Hz 400 (± 10%) / 3 / 50
Number of refrigerant circuits 2
Start-up Type SD+FI SD+FI SD+FI SD+FI SD+FI SD+FI
Min÷Max capacity steps % 13% ÷ 100% 14% ÷ 100% 13% ÷ 100% 17% ÷ 100% 15% ÷ 100% 14% ÷ 100%
COMPRESSOR
Number 2
Type 1 STEP SCREW + 1 INVERTER SCREW
INTERNAL HEAT EXCHANGER (EVAPORATOR)
Number 1
Type Shell & tube (Pure counterflow)
Water connections inch 8 8 10 10 10 10
EXTERNAL HEAT EXCHANGER (COILS)
Number 14 14 16 18 20 22
Type MCHX - Al/Alloy
FAN
Number 14 14 16 18 20 22
Air flow m³/h 267.480 267.480 305.640 343.800 381.960 420.120
Total input power kW 16.1 16.1 18.4 20.7 23.0 25.3
REFRIGERANT
Type / GWP R134a / 1430
Charge 1 / 2 (1)
kg
76 / 76 88 / 88 93 / 93 102 / 102 114 / 114 114 / 114
tCO
2
eq
108,7 / 108,7 125,8 / 125,8 133,0 / 133,0 145,9 / 145,9 163,0 / 163,0 163,0 / 163,0
Type / GWP R513A / 631
Charge 1 / 2 (1)
kg
76 / 76 88 / 88 93 / 93 102 / 102 114 / 114 114 / 114
tCO
2
eq
48,0 / 48,0 55,5 / 55,5 58,7 / 58,7 64,4 / 64,4 71,9 / 71,9 71,9 / 71,9
DESUPERHEATER
Number 2
Type PHE
WEIGHT
ShippinG kg 6341 7033 7485 8212 8596 8731
Operating kg 6617 7412 7852 8579 8963 9162
DIMENSIONS
Length mm 8868 9920 10972 12024 13076 13076
Width mm 2192 2192 2192 2192 2192 2192
Height mm 2590 2590 2590 2590 2590 2590
(1) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.
* Voltage supply tolerances: +/- 10% of the nominal Voltage (400V) for short term application; +/-5% of the nominal Voltage (400V) for continuous application
** High Temperature Units (HT), data with fans at max speed (1100 Rpm)
*** HPF Units, data with fans at max speed (1100 Rpm)