IOM SYSCREW AIR EVO HSE
45
English
8 - Technical Data (continued)
8.2 Technical data
SYSCREW AIR EVO HSE STD / HT / HPF 380 440 510 590 660 730
Power supply* V/Ph/Hz 400 (± 10%) / 3 / 50
Number of refrigerant circuits 2
Start-up Type PW+FI PW+FI PW+FI PW+FI SD+FI SD+FI
Min÷Max capacity steps % 22% ÷ 100% 18% ÷ 100% 16% ÷ 100% 14% ÷ 100% 13% ÷ 100% 15% ÷ 100%
COMPRESSOR
Number 2
Type 1 STEP SCREW + 1 INVERTER SCREW
INTERNAL HEAT EXCHANGER (EVAPORATOR)
Number 1
Type Shell & tube
Water connections inch 6 6 8 8 8 8
EXTERNAL HEAT EXCHANGER (COILS)
Number 8 10 10 10 12 12
Type MCHX - Al/Alloy
FAN
Number 8 10 10 12 14 14
Air flow m³/h 183.960 230.040 230.040 276.120 321.840 321.840
Total input power kW 12,0 15,0 15,0 18,0 21,0 21,0
Total input power ** kW 20,5 25,6 25,6 30,7 35,8 35,8
Total input power *** kW 24,0 30,0 30,0 36,0 42,0 42,0
REFRIGERANT
Type / GWP R134a / 1430
Charge 1 / 2 (1)
kg
33 / 33 41 / 41 46 / 46 51 / 51 65 / 65 68 / 68
tCO
2
eq
47,2 / 47,2 58,6 / 58,6 65,8 / 65,8 72,9 / 72,9 93,0 / 93,0 97,2 / 97,2
Type / GWP R513A / 631
Charge 1 / 2 (1)
kg
33 / 33 41 / 41 46 / 46 51 / 51 65 / 65 68 / 68
tCO
2
eq
20,8 / 20,8 25,9 / 25,9 29,0 / 29,0 32,2 / 32,2 41,0 / 41,0 42,9 / 42,9
DESUPERHEATER
Number 2
Type PHE
WEIGHT
Shipping kg 3747 4117 4651 4995 5392 5931
Operating kg 3896 4259 4897 5241 5620 6207
DIMENSIONS
Length mm 4660 5712 5712 6764 7816 7816
Width mm 2192 2192 2192 2192 2192 2192
Height mm 2510 2510 2510 2510 2510 2510
(1) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.
* Voltage supply tolerances: +/- 10% of the nominal Voltage (400V) for short term application; +/-5% of the nominal Voltage (400V) for continuous application
** High Temperature Units (HT), data with fans at max speed (1100 Rpm)
*** HPF Units, data with fans at max speed (1100 Rpm)