IOM SYSCREW AIR EVO HSE
32
6 - Control (continued)
ANALOG OUTPUTS - control board
Variable Name Type Description
Y1
0/10Vdc
Inverter fans Circuit 1 Step 2
Y2
0/10Vdc
Inverter fans Circuit 1 Step 1
Y3
0/10Vdc
Inverter fans Circuit 2 Step 2
Y4
0/10Vdc
Inverter fans Circuit 2 Step 1
Y5
0/10Vdc
Inverter pump evaporator
Y6
0/10Vdc
Not used
DIGITAL OUTPUTS - control board
Variable Name Type Description
NO1
SPST
Evaporator heater status
NO2
SPST
Compressor 1 Circuit 1 Solenoid CR1 status
NO3
SPST
Compressor 1 Circuit 1 Solenoid CR2 status
NO4
SPST
Compressor 1 Circuit 1 Solenoid CR3 status
NO5
SPST
Compressore 1 circuito 1 PartWindingA status
NO6
SPST
Compressore 1 circuito 1 PartWindingB status
NO7
SPST
Pump status
NO8
SPDT
Alarm status
NO9
SPST
Not used
NO10
SPST
Not used
NO11
SPST
Compressor cranckase heater status
NO12
SPDT
Not used
NO13
SPDT
Not used
NO14
SPDT
Not used
NO15
SPDT
Circuit 1 fans step 2 (group with fans > ) Status
NO16
SPST
Circuit 1 fans step 1 (group with fans < ) Status
NO17
SPST
Circuit 2 fans step 2 (group with fans > ) Status
NO18
SPST
Circuit 1 fans step 1 (group with fans < ) Status
DIGITAL OUTPUTS * - expansion card
Variable Name Type Description
NO1
-
ECO valve system 1 status
NO2
-
ECO valve system 2 status
NO3
-
Liquid injection valve system 1 status
NO4
-
Not used
NO5
-
Share fan deck fans (on-off) status
NO6
-
Not used
List of parameters - IN/OUT MENU (continued)