8 Refrigerant circuit
All the units are equipped with two independent and separate refrigerant
circuits.
Each refrigerant circuit is equipped with liquid line and discharge line shut-off
valves, filter-drier with solid core, sight glass and electronic expansion valve.
Heat pump units (VLH) are additionally provided with 4-way reversing valves,
suction accumulators and liquid receivers.
Total heat recovery units (VLR) are additionally provided with 4-way reversing
valves and liquid receivers.
9 Control panel
A new optimized control with an easy-friendly interface, manages unit
operation under different load and temperature condition and can provide:
Compressor management
o Power on/off
o Anti-cycle
o Tandem / trio unloading for high pressure, high temperature and/or
high compressor pressure ratio
Chilled and hot water temperature regulation (return water temperature
RWT - P+I type or leaving water temperature LWT - neutral band type)
Automatic control of suction superheating though electronic expansion
valve with optimized functions (cooling, heating, start-up and defrost)